| Models: | Bulb Life: |
|---|
| See Table 1. | 18000 hours Accessories: UVL-FCU-LAMP Replacement UV-C lamp Table 1. Models. |
|---|
| Part Number | Description Replacement Lamp Power Supply* |
|---|
| UVL-FCU-LINE | FCU/PTAC 110-277 Vac, 50/60 Hz UVL-FCU-LAMP (MFG# TUVP-ST-CE) (MFG# TUVL-200EZ) |
|---|
| UVL-FCU-LOW | FCU/PTAC 18-32 Vac, 60 Hz UVL-FCU-LAMP (MFG# TUVP-ER) (MFG# TUVL-200EZ) 31-00403-02 |
|---|
| WARNING | A Only qualified technicians should install this product. Install so that direct UV light is not visible in occupied space. Install in accordance with relevant building codes. Read instructions carefully including safety B C warnings. |
|---|
| B. “LOW” Power Supply* | D E F G H |
|---|
| E. Replacement O-Rings | I J WARNING |
|---|
| K | L Fig. 1. Parts WARNING Be careful of damage to equipment. |
|---|
| depending on model | Ultraviolet light can cause color fading or degraded structure of plastic material found in HVAC equipment, avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation. WARNING UV Light Hazard. Harmful to bare skin and eyes. Can cause temporary or permanent loss of vision. Do not look at the UV lamp when lighting is on. Use indicator light on t |
|---|
| When Installing This Product… | Can cause electrical shock or equipment damage. Do not connect to power before installation is them could damage the product or cause a hazard- complete. ous condition. the product to make sure the product is suitable for Installation in PTACs and Fan Coils your application. |
|---|
| technician. | lamp and power supply. (Fig. 2-Fig. 4) operation as provided in these instructions. light leakage into the room. 3. Locate lamp so it irradiates wet side of coil and/or blower areas where fouling is present. 4. Mount lamp with magnet or self-tapping screws. 5. Apply warning/replacement lamp sticker to outside of unit (see Sight Glass Installation). PTAC |
|---|
| Front | Side Fig. 2. Example PTAC Installation Fan Coil (horizontal) |
|---|
| Breakable Glass Hazard. | Sight glass may not be needed if reflected UV light is |
|---|
| Can cause personal injury. | visible. Be careful when inserting bulb(s) into lamp base. 1. Find a suitable location on the outside of the unit Wear protective gloves when handling bulb(s). near the UV lamp installation and apply the warn- ing/lamp replacement sticker. 2. Drill a ½ inch hole through the orange circle on the sticker. Press the UV safety viewport into the hole. |
|---|
| MERCURY NOTICE | 3. When power is connected the sight glass can be used to confirm the UV lamp is operating. This device contains mercury in the sealed ultraviolet bulb(s). Do not place your used bulb(s) in the trash. Dispose of properly. The UVL-FCU components are designed to with- stand the typical ambient temperatures found Fig. 6. Sight Glass Installation near fan coil and PTAC heating elements up to a constan |
|---|
| may be mounted near the heating elements. | Can cause personal injury. IMPORTANT Check which power supply is included with your UVL-FCU kit before connecting to power. Use the wiring diagrams below (Fig. 7) to connect to power. The low voltage power supply (18 to 32 VAC) is 24 VAC marked “LOW”. The high voltage (120 to 277 VAC) power supply is marked “LINE”. 18 - 32 VAC Power Supply 110 - 277 VAC Power Supply Fig. 5. Power Supply Installati |
|---|
| UV LAMP | UV LAMP |
|---|
| BLUE CABLE | BLUE CABLE |
|---|
| L1-BLACK | DISCONNECT |
|---|
| AIR HANDLER | BLACK |
|---|
| COMMON | / BLUE 24 VAC 120-277 VAC 24 VAC L 2 or N-WHITE |
|---|
| RED | POWER SUPPLY GND-GREEN POWER SUPPLY TRANSFORMER HOT / RED 24 VAC TRANSFORMER |
|---|
| Low-voltage "LOW" wiring | Line-voltage "LINE" wiring Fig. 7. Electrical Connections |
|---|
| Connect Lamps and Cables | MAINTENANCE |
|---|
| proper water-resistant seal. | humidity. They are warranted for 2 years of UVC output, to 60% of their original output. Sizing guidelines are based on the end of lamp life output levels. |
|---|
| Align Flanges | 2. Honeywell UV lamps are rated for two years germicidal illuminate, but does NOT have any germicidal effectiveness. Bulbs must be replaced on schedule for the system to function properly. IMPORTANT Use only Honeywell replacement lamps. Use of |
|---|
| Fig. 8. UV Lamp Connection | replacement lamps from other manufacturers voids the warranty. See Table 1 for replacement lamp part numbers. ® U.S. Registered Trademark |
|---|
| customer.honeywell.com | ©2020 Honeywell International Inc. 31-00403—02 M.S. Rev. 09-20 |
|---|