| work. | • Easy mount chassis. |
|---|
| expansion. | Transmitter |
|---|
| FM APPROVED to UL ANSI 864. | • Four Style Y (Class B) or two Style Z (Class A) NAC circuits. |
|---|
| Controls And Indicators | • Selectable strobe synchronization per NAC for System Sensor, Wheelock, and Gentex devices. |
|---|
| LED INDICATORS | • Certified for seismic applications when used with the appropriate |
|---|
| • AC POWER (green) | seismic mounting kit |
|---|
| • FIRE ALARM (red) | • Seamless integration between fire and mass notification with the |
|---|
| • SUPERVISORY (yellow) | ECC-50/100 Emergency Command Center via ANN-BUS con- nections. • ALARM SILENCED (yellow) |
|---|
| • SYSTEM TROUBLE (yellow) | • ECC-FFT Firefighter Telephone Option |
|---|
| • MAINTENANCE/PRESIGNAL (yellow) | • ANN-BUS for connection to following optional modules Note: cannot be used if ACS annunciators are used. • DISABLED (yellow) |
|---|
| • BATTERY FAULT (yellow) | – TIS-ANN-80 Remote LCD Annunciator |
|---|
| • GROUND FAULT (yellow) | – ANN-RLY Relay Module – ANN-LED Annunciator Module |
|---|
| MEMBRANE SWITCH CONTROLS | – ANN-RLED Annunciator Module (alarms only) |
|---|
| • ACKNOWLEDGE/STEP | • Compatible with SWIFT® wireless devices • ALARM SILENCE • DRILL |
|---|
| ‘ | DA-47110:B3 • 2/20/2019 — Page 1 of 6 |
|---|
| Standard Features | • Optional 4XTMF module (conventional reverse polarity/city box transmitter). detectors and 159 monitor, control, or relay modules). using a Windows®-based software package (download PS-Tools mm²) using twisted, unshielded wire (see Wire Table on page 5). locally to the Unimode 9600UDLS in less than one minute. |
|---|
| NOTIFICATION APPLIANCE CIRCUITS (NACS): | Autoprogramming: Command the Unimode 9600UDLS to program itself (takes less than 30 seconds). In the Auto-Program mode, the control modules (CMF-300 or CMF-300-6). The four Class B stores the device types, and addresses found, and then loads NACs can be converted to two Class A NACs with the NACKEY default values for all options (General Alarm). It also checks for two (included). or more devices s |
|---|
| each NAC circuit | of more than 50 adjectives/nouns, such as “FLR 3 HALLWAY,” or Note: Maximum 24 VDC system power output is shared among enter custom labels letter-by-letter. Use recall function to repeat pre- all NAC circuits and 24 VDC special application auxiliary power viously used label. outputs. Total available output is 7.0 amps. Program Check: Automatically catch common errors, such as con- |
|---|
| ADVANCED FIRE TECHNOLOGY: | trol modules not linked to any zone or input point. |
|---|
| • Automatic drift compensation. | Maintenance Alert The Unimode 9600UDLS continuously monitors each smoke detec- |
|---|
| PROGRAMMING AND SOFTWARE: | tor and is capable of reporting maintenance conditions. This reduces PC (using the standard PS-Tools Windows® utility). |
|---|
| • Two-level user-programmable passwords. | Automatic Test Operation |
|---|
| selected from an internal library file. | tor every two hours. Failure to meet the test limits causes an AUTO Terminal Blocks AC Power – TB1: 120 VAC, 60 Hz, 3.0 amps. Wire size: minimum 9600UDLS with USB port for local upload/download. Battery (lead acid only) – TB2: Maximum charging circuit: Normal monitor modules, ACS Series annunciators, LCD-80F remote ity: 26 AH. Minimum battery 12 AH. Unimode 9600UDLS cabinet annunciator, or ANN-80 |
|---|
| board. | Box. |
|---|
| ments. | Communication Loop – (standard) TB8: 24 VDC nominal, 27.6 |
|---|
| • History file with 1,000-event capacity. | VDC maximum. Maximum length: 10,000 ft. (3048 m) total twisted, |
|---|
| or 32 ACS Series annunciators. | or 100 mA (normal). Maximum loop resistance: 40 ohms. Super- |
|---|
| tion is excessive. | Nominal operating voltage: 24 VDC. Current limit: fuseless, elec- tronic, power-limited circuitry. Maximum signaling current per circuit: 3.0 amps special application, 300mA regulated. End-of-Line Resis- |
|---|
| out. | Unimode Device Compatibility Document for listed compatible |
|---|
| • Point trouble identification. | devices. |
|---|
| • Local piezo sounder. | Programmable and Trouble Output Relays – TB5: Contact rating: (NFPA 72 compliant). |
|---|
| Four-Wire Resettable Smoke Detector Power | PRN Series: UL listed compatible event printer which uses tractor- |
|---|
| Power-limited circuit, non-supervised. | BEAM355S: Intelligent beam smoke detector with integral sensitiv- ity test. rate-of-rise option. |
|---|
| Ordering Options | H355HT/H365HT(-IV): Fast-response, low-profile heat detector that |
|---|
| printed circuit board, and cabinet. | designed to provide open area protection |
|---|
| with Unimode 9600UDLS). | detector CMF-300: Addressable Control Module for one Style Y/Z (Class B/ CRF-300: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500. MDF-300: Dual Monitor Module. Same as MMF-300 except it pro- vides two Style B (Class B) only IDCs MMF-300: Addressable Monitor Module fo |
|---|
| amp relays. | A) IDC. MMF-302: Similar to MMF-300, but may monitor up to 20 conven- ule mounted inside 2F cabinet (optional). Mount up to six modules on a CHS-6 chassis |
|---|
| charging greater than 25 AH batteries. | SMB500: Used to mount all modules except the MMF-301 and M301 |
|---|
| AH batteries. | in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F DA-47110:B3 • 2/20/2019 — Page 3 of 6 Unimode 9600LS |
|---|
| ADDRESSABLE | SMOKE DETECTORS FIRE ALARM CONTROL PANEL SD355/T, SD365/T, CP355 EIA-485 ACS/ANN-BUS |
|---|
| ANNUNCIATORS | HEAT (2-data wires, DETECTORS 2-power wires) H355/R, H365R AC K |
|---|
| E | 8 FORM-C, 5-AMP RELAYS ALARM TROUBLE (optional, order ACM-8RF) FIRE ALARM ANNUNCIATOR |
|---|
| TIS-ANN-80 | NACs (Notification |
|---|
| Appliance Circuits) | DUCT DETECTORS |
|---|
| BELLS, SIGNALS, STROBES | D355PL EIA-232 |
|---|
| 接口 | DACT-UD2 for Central Station reporting INTELLIGENT BEAM DETECTORS |
|---|
| PRINTER | Optional BEAM355, BEAM355S, |
|---|
| REVERSE | OSI-RI-FL POLARITY/ CITY BOX OUTPUT (4XTMF) |
|---|
| ON | A B |
|---|
| C | D CN1 MONITOR/CONTROL MMF-300, MDF-300, MMF-302, CMF-300, CRF-300, I300, CDRM-300 CN2 4XTMF |
|---|
| PSTN | PHONE TO AP FROM AP OUT 2 OUT 1 INPUT 2 INPUT 1 TAMPER GND +24V |
|---|
| Reverse Polarity Module | IPDACT Internet Protocol DACT |
|---|
| WIRELESS | MINI MONITOR |
|---|
| Wireless | GATEWAY MMF-301 |
|---|
| Monitor | W-GATE Module ADDRESSABLE |
|---|
| W-MMF | MULTI-MODULES |
|---|
| Relay | MMF-302-6, |
|---|
| Module | CMF-300-6, CRF-300-6 |
|---|
| W-CRF | ISO-6 Wireless Photo Detector W-SD355 Wireless Pull Station |
|---|
| W-BG12LX | PULL STATION TIS-BG12LX DA-47110:B3 • 2/20/2019 — Page 5 of 6 |
|---|
| System Capacity | cm.) wide x 5.21" (13.23 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. |
|---|
| • | Intelligent Signaling Line Circuits.....................1 expandable to 2 |
|---|
| Electrical Specifications | 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's |
|---|
| • Primary input power: | standby batteries and the electronic components may be adversely 120 VAC, 50/60 Hz, 3.0 A. affected by extreme temperature ranges and humidity. Therefore, it 240 VAC, 50 Hz, 1.5 A. is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – |
|---|
| • Battery: 27.6 VDC @ 1.0 A (max). | 80°F. Maximum battery charger capacity: 26 AH. Minimum battery: 12 AH. Unimode 9600UDLS cabinet holds maximum of two 18 AH bat- Agency Listings and Approvals |
|---|
| teries. | The listings and approvals below apply to the Unimode 9600UDLS |
|---|
| limited. | certain approval agencies, or listing may be in process. Consult fac- tions for four Style Y (Class B) or two Style Z (Class A) NACs. • FM APPROVED: to UL ANSI 864 Maximum signaling current per circuit: 3.0 amps special applica- • CSFM: 7165-1574:206 tion, 300mA regulated. • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic). End-of-Line Resistor: 4.7 K ohms, ½ watt (P/N 71252 UL listed) |
|---|
| for Style Y (Class B) NAC. | • CBC 2007 (Seismic) Supervised and power-limited. Refer to panel documentation and Unimode Device Compatibility NFPA Standards Document for listed compatible devices. The Unimode 9600UDLS control panel complies with the following Form-C Relay: Contact rating: 2.0 A @ 30 VDC (resistive) 0.5 A @ 30 VAC (resistive). – LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi- sory). nal): Up to 1.5 |
|---|
| Limited, non-supervised. | 4XTMF). Refer to Unimode Device Compatibility Document for listed com- – REMOTE STATION (Automatic, Manual and Waterflow) |
|---|
| patible devices. | (Requires 4XTMF where DACT-UD2 is not accepted.) |
|---|
| TB3, Terminals 3 (+) & 4 (-): | – CENTRAL STATION (Automatic, Manual and Waterflow, and |
|---|
| Maximum ripple voltage: 10 mVRMS | Sprinkler Supervised). Total DC current available from each output is up to 1.5 A. – OT (Other Technologies-PSDN) For use with IPDACT. Power-limited, non-supervised. TB3, Terminals 5 (+) & 6 (-): Maximum ripple voltage: 10 mVRMS Total DC current available from each output is up to 1.5 A. Power-limited, non-supervised. |
|---|
| Cabinet Specifications | LiteSpeed™ is a trademark; and FireLite® Alarms and SWIFT® are registered trademarks of Honeywell International Inc. Windows® is a trademark of the This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change witho |
|---|