| General Notes on Strobes (Continued) | Engineer’s Specifications (Continued) Listed for -31°F to 150°F (-35°C to 66°C) and maximum |
|---|
| humidity of 95%. | The Series MT-12/24 audible appliance may be installed indoor or outdoor with the proper back box. used by UL to identify the voltage range. Prior to this require 75 cd @ -31°F (-35°C) and full temperature range change UL used the terminology “Listed Voltage of -31°F to 150°F refer to Data Sheet S9004 and/or Instal- |
|---|
| Range”. | lation Instructions P84150. |
|---|
| Engineer’s Specifications | WARNING! |
|---|
| with Cooper-Wheelock’s Sync Protocol. | AGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. |
|---|
| synchronized default flash rate. | TO DESIGN AND INSTALLATION OF THESE PROD- UCTS, PARTICULARLY IN RETROFIT INSTALLA- GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 |
|---|
| CS-2247 Rev. A page 2 of 4 | www.gamewell-fci.com AUDIBLE SIGNAL AND STROBE OPERATE INDEPENDENTLY MT SIGNAL |
|---|
| FROM | + + TO NEXT FROM + +TO NEXT |
|---|
| PRECEDING - | - APPLIANCE OR |
|---|
| APPLIANCE, | EOLR AUDIBLE OR OR EOLR |
|---|
| SM/DSM | FACP |
|---|
| PS-12/24-8MP | + - FROM + +TO NEXT |
|---|
| 供電 | PRECEDING - - STROBE |
|---|
| OR FACP | SIGNAL OR EOLR APPLIANCE, |
|---|
| PRECEDING | RED APPLIANCE WIRING METHOD PER NFPA/NEC. |
|---|
| APPLIANCE - | - OR EOLR |
|---|
| + - | + - |
|---|
| STROBE | AUDIBLE Figure 1 MT Signal Wiring Ordering Information |
|---|
| Model Number | Input Voltage Rated Candela Mounting Options*** Agency Approvals UL MEA CSFM FM BFP |
|---|
| MT-12/24-R” | 12/24 - D,E,F,L,M,O,P,R X X X X X |
|---|
| MT-241575W-FR* | 24 15 (75 or AXIS) D,E,F,L,M,O,P,R X X X X * |
|---|
| MT-2475W-FR | 24 75 D,E,F,L,M,O,P,R X X X X * |
|---|
| MTWP-2475W-FR** | 24 75** (@-31°F/-35°C) M X X X X * |
|---|
| MT4-115-R | 115 VAC - D,E,J,K,N,O,R X X X X X |
|---|
| MT4-115-WH-VFR## | 115 VAC 15 D,E,J,K,N,O,R X X X X X |
|---|
| Sync Models | Input Voltage Average Current (AMPS) Mounting Options UL MEA CSFM FM BFP |
|---|
| SM-12/24-R | 12 or 24 W X X X X X |
|---|
| DSM-12/24-R | 12 or 24 W X X X X X GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 |
|---|
| www.gamewell-fci.com | CS-2247 Rev. A page 3 of 4 SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAU- TIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. |
|---|
| Tone | Average Mean Current Ratings dBA Reverberant Ratings Per UL 464 dBA Anechoic Ratings |
|---|
| @24 VDC | @ 12 VDC @ 24 VDC @ 12 VDC @ 12 and 24 VDC |
|---|
| HI | STD HI STD HI STD HI STD HI STD |
|---|
| Horn | 0.040 0.025 0.100 0.020 92 87 90 77 99 93 |
|---|
| Bell | 0.020 0.013 0.031 0.010 86 80 85 69 92 87 |
|---|
| March Time Horn | 0.040 0.025 0.100 0.020 89 84 89 74 99 93 |
|---|
| Code-3 Horn | 0.040 0.025 0.100 0.020 88 83 88 73 99 93 |
|---|
| Code-3 Tone | 0.028 0.017 0.060 0.015 85 80 84 70 95 90 |
|---|
| Slow Whoop | 0.048 0.026 0.100 0.025 90 89 89 75 99 94 |
|---|
| Siren | 0.036 0.023 0.082 0.020 89 84 89 75 98 93 |
|---|
| HI/LO | 0.021 0.014 0.044 0.012 86 81 86 71 93 88 Note 1: If the strobe and audible operate on the same circuit, add the strobe current from Table 2 to the audible current from Table 1. For Peak and Inrush current across the listed voltage range refer to Installation Instructions. Note 2: *Average RMS Current is per UL average RMS method and Average Mean Current is per UL average mean method. For rated In |
|---|
| UL 12 and 24 VDC Voltage Range | Average RMS Current* Average Mean Current |
|---|
| MT-241575W | MT2475W MT-121575W MTWP2475W 16.0 VDC .101 .215 - .158 24.0 VDC .064 .140 - .107 33.0 VDC .047 .114 - .090 8.0 VDC - - .336 - 12.0 VDC - - .179 - 17.5 VDC - - .136 - NOTES on dBA/CURRENT RATINGS TABLE 1 and 2 ABOVE: 1) Anechoic dBA is measured on axis in a non-reflective (free field) test room using fast meter response. For peak dBA (measured with peak meter response), add 5 dBA to typical anechoi |
|---|
| Tones | Pattern Description |
|---|
| Hi/Lo | 1000/800 Hz (0.25 sec. ON/Alternate) Table 3: Alarm Tones Disclaimer: Cooper-Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state a |
|---|
| CS-2247 Rev. A page 4 of 4 | www.gamewell-fci.com |
|---|