| Backbox Mounting | AC power, TB8 Battery (sealed lead-acid only), J8 |
|---|
| Ordering Information | Maximum charging circuit: normal flat charge 27.6 VDC @ 0.8 A. Maximum battery charger capacity: |
|---|
| F404 | Four-zone conventional FACP. 18 AH battery. Two 7 AH batteries can be |
|---|
| XRM-24 | 120 VAC, 100 VA transformer, expands NAC power from 3.0 housed in the FACP cabinet.Larger batteries |
|---|
| to 5.0 Amps. | require a separate battery box i.e. BB-17F. Initiating device circuits, TB3 |
|---|
| CAC-4 | Class A converter module. Used to convert Style B (Class Alarm zones 1 – 4. Power-limited circuitry. B) IDC to Style D (Class A) and Style Y (Class B) NAC to Operation: all zones Style B (Class B). Style Z (Class A). The module connects to J1 on the Flex Normal operating voltage: nominal 22 VDC. 404 circuit board. Alarm current: 15 mA minimum. Standby current: 4 mA. 4XTMF Transmitter module. Short |
|---|
| cators with Flex 404. | circuitry. Normal operating voltage: nominal 24 VDC. |
|---|
| PRO-411 | Programmer used with 411UD. Maximum signaling current: 2.5 A total with standard transformer; 5.0 A total (2.5 |
|---|
| SAN-404 | Remote annunciator (RZA-4XF), mounts in a single-gang maximum per NAC) with optional trans- |
|---|
| box. | former. End-of-line resistor: 4.7K ohm, 1/2 watt |
|---|
| BB-17F | Battery box, required to house two batteries greater than 7 |
|---|
| AH, to a maximum of 18 AH. | (P/N 71252). Form-C relays |
|---|
| DP-FLEX | Dress panel. Trouble relay TB5 (fail-safe). Alarm relayTB6. |
|---|
| TR-1-R | Trim ring for semi-flush mounting. Contact ratings: 2.0 A @ 30 VAC (resistive). 52194 Flex 404 Installation and Maintenance Manual. Auxiliary outputs Resettable power, TB1 Power-limiting circuitry. Maximum available current: 500 mA, appropriate for powering four-wire smoke detectors. See note under nonresettable. Nonresettable power, TB1 Power-limiting circuitry. Operating voltage: nominal 24 VDC. |
|---|
| Gamewell-FCI | Backbox: 15.0" (38.10 cm) high x 14.5" 12 Clintonville Road (36.83 cm) wide x 3.0" (7.62 cm) deep. Northford, CT 06472-1610 Phone: 203-484-7161 |
|---|
| Fax: 203-484-7118 | Specifications and wiring information are provided for information only and are |
|---|
| www.gamewell-fci.com | believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring |
|---|
| A Honeywell Company | instructions shipped with the product shall always be used for actual installation. For |
|---|
| © 2006 Gamewell-FCI | more information, contact Gamewell-FCI. |
|---|