| the main CPU. | tus and control. The alphanumeric display is designed to communicate over the serial communications network. |
|---|
| during a polling sequence. | require state-of-the-art life-safety systems. The embedded CPU offers users unrivaled reliability without sacrificing With compatible analog sensors and addressable input and control interface devices, and its remote status and control capabilities, the IF602SS provides system engineers with all the tools necessary to design effective system solutions |
|---|
| IF602SS Power Supply | for any application. The control panel furnished and installed shall be capable of supporting 396 addressable devices and two analog loops. The panel shall use a fully digital Signaling Line Cir- cuit (SLC) protocol. The panel shall contain four on-board Notification Appliance Circuits (NACs) that support the mul- tiple synchronization protocols. The panel shall use a 160- character Liquid Crystal |
|---|
| CS-2490 Rev. B page 2 of 3 | www.gamewell-fci.com |
|---|
| Specifications | Ordering Information |
|---|
| Standby Current: | 0.160A |
|---|
| Alarm Current: | 0.226A plus signaling circuit GWIF602SS-198R IF602SS Analog Addressable System with Velociti consisting of the following: power, plus 0.002A for master box, • IF602SS common control |
|---|
| or plus 0.022A for reverse-polarity | • 8 amp. main power supply |
|---|
| Input Power: | 120 VAC, 4.0A; or 240 VAC, 2.0A • One (1) analog circuit module (198 analog addressable points) |
|---|
| Auxiliary Output: | • Standard cabinet assembly |
|---|
| S+/S–, A+/A–: | 2.0 A maximum (CAB-602R) |
|---|
| Common Relays: | 1.0A @ 30 VDC, or 0.5A @ 250 Standard Cabinet: |
|---|
| VAC | 20.0” H x 14.0” W x 4.5” D (50.8 H x 35.6 W x 11.4 D cm) |
|---|
| Notification Appliance Circuits: | GWIF602SS-396R IF602SS analog addressable system |
|---|
| Circuits: | Four Class B, two Class A with Velociti, consisting of the following: |
|---|
| Output: | 3.0A maximum@24 VDC per circuit. • IF602SS common control |
|---|
| Maximum 7.5A total for all circuits | • 8 amp main power supply • Two (2) analog circuits module (396 analog addressable points) |
|---|
| Analog SLC: | 198 396 • Standard cabinet assembly |
|---|
| Panel Dimensions: | (50.8 H x 35.56 W x 11.43 D cm) |
|---|
| Standard Cabinet: | 20.0" H x 14.0" W x 4.5" D 52358 IdentiFlex 602SS Analog/Addressable (50.8 H x 35.6 W x 11.4 D cm) Fire Alarm Control Panel Installation and Operation Manual |
|---|
| Battery Storage Dimensions: | GW31077 CTM-602, city-tie/remote signaling (15.24 H x 22.86 x 11.43 D cm) GW31078 ISO-232, RS-232 serial-port isolator |
|---|
| Relative Humidity: 93% non-condensing | module for 602 Series panels. |
|---|
| Temperature | GW31079 CLA-602, Class “A” adapter module for 32°F – 120°F (0°C – 49°C) SLC, 602 Series panels. |
|---|
| GW70703 | Coiled Programming Cable GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 |
|---|
| www.gamewell-fci.com | CS-2490 Rev. B page 3 of 3 |
|---|