| tem. | D350RPL 20.32 m/sec). |
|---|
| meters) wide. | RA400Z RTS451 RTS451KEY cations for Signaling Line Circuit (SLC) wiring. Consult the con- |
|---|
| 安裝 | trol panel specifications for wiring requirements before wiring the detector loop. The D350PL(A) and D350RPL(A) detectors are designed for ease of wiring; their housing provides a termi- nal strip with clamping plates. two LEDs on each duct smoke detector light to provide local vis- ible indication. |
|---|
| used if desired. | devices is determined by the control panel and its ability to sup- ply LED current. Refer to the control panel installation manual for details. DF-52398:A • 12/29/06 — Page 1 of 4 On to other Detectors on the Loop. 6821wir1.wmf D350PL(A) Duct Smoke Detector using a UL or ULC Listed control panel. COMMON RA400Z D350PL(A) Duct Smoke Detector |
|---|
| Detector | with an optional RA400Z(A). RA400Z Terminals 6821wir2.wmf RTS451KEY D350PL(A) Duct Smoke Detector COMMON COM (+) COM (–) with RTS451(A)/RTS451KEY(A). RA400Z TEST 6821wir3.wmf NOTE: For RTS451(A), Terminal 3 is not |
|---|
| LED | RESET RTS451/RTS451KEY Inlet Tube Selection |
|---|
| Outside Duct Width | Inlet Tube* |
|---|
| Up to 2 feet (0.6096 m) | ST-1.5(A) 2 to 4 feet (0.6096 to 1.2192 m) ST-3(A) 4 to 8 feet (1.2192 to 2.4384 m) ST-5(A) 8 to 12 feet (2.4384 to 3.6576 m) ST-10(A) *Inlet tube is required and must be purchased separately. Order One inlet tube for each duct smoke detector ordered. D350RPL(A) Duct Smoke Detector using a UL-Listed control panel: 7006wir1.wmf NOTE: 1) Jumper J1 shunt must be installed for 2-W applications. J1 shu |
|---|
| D350RPL(A) Duct Smoke Detector | D350RPL(A) Duct |
|---|
| with an optional RA400Z(A): | Smoke Detector with RTS451(A)/RTS451KEY(A): 7006wir2.wmf 7006wir4.wmf 7006wir3.wmf DF-52398:A • 12/29/06 — Page 3 of 4 |
|---|
| Product Line Information | Operating temperature range: 32° to 131°F (0° to 55°C). Operating humidity range: 10% to 93% relative humidity (non- condensing). Storage temperature range: –22°F to +158°F (–30°C to +70°C). Duct air velocity: 100 to 4,000 feet/min (0.5 to 20.32 m/s). Shipping weight: 3.90 lbs. (1.8 kg). |
|---|
| RA400Z(A): Remote annunciator alarm LED. | refer to PA400 data sheet DF-50727. RA400Z(A): 0 mA D350RPL(A) CURRENT REQUIREMENTS (USING NO ACCESSORIES) response time; 2 second power-up time. 24 VAC, 50/60 Hz power supply voltage: 65 mA RMS maxi- mum standby current; 182 mA RMS maximum alarm current; 3 to 10 second alarm response time; 2 second power-up time. 120 VAC, 50/60 Hz power supply voltage: 44 mA RMS maxi- |
|---|
| Specifications | mum standby current; 52 mA RMS maximum alarm current; 3 to 10 second alarm response time; 2 second power-up time. 220/240 VAC, 50/60 Hz power supply voltage: 25 mA RMS |
|---|
| Operating voltage range: 15 to 30 VDC. | maximum standby current; 30 mA RMS maximum alarm current; |
|---|
| condensing). | The listings and approvals below apply to D350PL(A) and D350RPL(A) Intelligent Low-Flow Photoelectric Smoke Duct Detectors. In some cases, certain modules may not be listed by |
|---|
| Shipping weight: 3.35 lbs. (1.5 kg). | factory for latest listing status. |
|---|
| • | ULC Listed: file CS6963 (D350PLA, D350RPLA). |
|---|
| FOR D350RPL(A) | • Maryland State Fire Marshal approved: Permit #2144. Fire•Lite® Alarms and System Sensor® are registered trademarks of Hon- eywell International Inc. ©2006 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. |
|---|