| www.gamewell-fci.com | GF11641_10 page 1 of 2 |
|---|
| Xtralis | ® VLP |
|---|
| Detector Mounting Box | 6SHFL¿FDWLRQV Supply Voltage: 18–30 VDC Dimensions |
|---|
| in | mm Power Consumption @ 24 VDC: |
|---|
| A | 13.8 350 No Display or Programmer |
|---|
| B | 8.9 225 Aspirator @ 3000 rpm Aspirator @ 4200 rpm |
|---|
| C | 2.75 70 Quiescent With Alarm Quiescent With Alarm |
|---|
| D | 2.25 57 Power 5.8 W 6.96 W 8.16 W 9.36 W |
|---|
| E | 1.37 35 Current 240 mA 290 mA 340 mA 390 mA |
|---|
| F | 1.75 44.5 Dimensions (WHD): |
|---|
| G | 0.87 22.0 13.8 in x 8.9 in x 4.9 in (350 mm x 225 mm x 125 mm) |
|---|
| H | 5.56 14.1 |
|---|
| I | 0.62 15.9 Weight: |
|---|
| J | 1.31 33.3 9 lbs (4.0 kg) including Display and Programmer modules |
|---|
| K | 1.33 34 IP Rating: IP30 |
|---|
| L | 0.94 23.8 |
|---|
| M | 2 51 Operating Conditions: |
|---|
| N | 0.83 21 Tested to: 14°–131°F (-10°C–55°C) |
|---|
| O | 5.56 141 Detector Ambient: 32°–103°F (0°C–39°C) (Recommended) |
|---|
| P | 1 25.4 Sampled Air: -4°–140°F (-20°–60°C) |
|---|
| Q | 0.44 11.1 Humidity: 10%–95% RH, non-condensing |
|---|
| R | 0.37 9.5 3OHDVHFRQVXOW\RXU;WUDOLVRI¿FHIRURSHUDWLRQRXWVLGH |
|---|
| S | 1.12 28.5 WKHVHSDUDPHWHUVRUZKHUHVDPSOHGDLULVFRQWLQXDOO\ |
|---|
| T | 1.19 30.2 DERYHREVIW REVP XQGHUQRUPDO |
|---|
| U 0.125 | 3.2 RSHUDWLQJFRQGLWLRQV Sampling Network: Aggregate pipe length: 650 ft (200 m) |
|---|
| Detector Termination Card | Maximum Single Length: 325 ft (100 m) Pipe Modelling Design Tool: ASPIRE2™ Pipe Size: External Diameter 1 in (25 mm) Internal Diameter 9/16 in–7/8 in (15–21 mm) Programmable Relays: 7 Relays, Contacts rated 2 A @ 30 VDC NO/NC Contacts Cable Access: 8 x 1 in (25 mm) knockouts in various positions Cable Termination: Screw terminals 30–12 AWG (0.2–2.5 sq mm) Alarm Sensitivity Range: 0.0015%–6.25% obs |
|---|
| Xtralis VESDA VLP | VLP-0XX XX (see below) Minimum 15 minutes, maximum 15 days. Recommended |
|---|
| Detector Configurations | VLP-0XX XX minimum period 1 day. During AutoLearn thresholds are 0=Blank Plate NOT changed from pre-set values. 1=Programmer 2=Display 4=Scanner Display 0=Standard Detector Orientation Software Features: 1=Inverted Detector Orientation Referencing: Compensation for external ambient 0=Standard Product 1=Custom (consult factory) conditions. Four Alarm Levels: Alert, Action, Fire 1 & Fire 2. Two Faul |
|---|
| Remote Programmer | VRT-100 Software Programmable Relays: 7. |
|---|
| Recessed Mounting Kit (Optional) | VSP-011 Maintenance Aids: Filter & Flow monitoring. |
|---|
| Hand-held Programmer | VHH-1000 Event reporting via VESDAnet or Event Log. |
|---|
| LQ6XE5DFN&RQ¿JXUDWLRQ | FRQWDFW;WUDOLV www.xtralis.com The Americas +1 781 740 2223 Asia +852 2297 2438 Australia and New Zealand +61 3 9936 7000 Continental Europe +41 55 285 99 99 UK and the Middle East +44 1442 242 330 The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the FRPSOHWHQHVVDFFXUDF\RUUHOLDELOLW\RIWKHFRQWHQWVRIWKLV |
|---|
| Doc. no. 11641_10 | Part: 18253 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 |
|---|
| GF11641_10 page 2 of 2 | www.gamewell-fci.com |
|---|