| www.gamewell-fci.com | GF13803_08 page 1 of 2 |
|---|
| Display Module (side view) | Display Module (front view) Specifications Supply Voltage: 18 to 30 VDC Power Consumption @ 24 VDC: |
|---|
| Module Only | In Remote Mounting Box (No relays) |
|---|
| Quiescent | With Alarm Quiescent With Alarm |
|---|
| 供電 | 1.6 W 2.2 W 2.4 W 3.0 W 5.3" Current 60 mA 80 mA 90 mA 110 mA (130 mm) Dimensions (WHD): Mounted in Remote Box - 5.5 in x 5.9 in x 3.4 in (140 mm x 150 mm x 85 mm) Operating Temperature: 32° to 103°F (0° to 39°C) Humidity: 10-99%RH non-condensing Alarm Indicators: High Intensity LEDs with 70 degree viewing angle Push Buttons Keys: 1.2" 4.1" (Mode/Test, Silence/Scan, Reset, Isolate) (30 mm) (105 mm |
|---|
| Remote Mounting Box | Mode/Test (Dual Function): Short press: Selects modes on the numeric display: |
|---|
| E | F Sensitivity, Smoke Level, and Zone Number. For LaserSCANNER displays, the First sector/pipe in alarm can be selected. Note: The current mode is indicated Dimensions by the appropriate LEDs. |
|---|
| in mm | Long press: Activates the Test Mode (6) “O” DIA. KNOCKOUTS: A 5.5 140 -2 TOP, -2 BACK |
|---|
| AND 1- EACH SIDE (2) | B 5.9 150 Silence (Silence/Scan): |
|---|
| C 2.75 70 | (Dual function on SCANNER only) D 2.36 60 E 1.75 44.5 Short press: Silences any alarm or fault warnings. TOP VIEW |
|---|
| F | 1.9 48 Flashing LEDs are permanently lit until the event is cleared |
|---|
| D | G 0.9 23 and the system reset. Only affects the local display. |
|---|
| J | J N H 0.98 25 |
|---|
| I | 1.1 27.5 Long press: Initiates the scanning of each pipe individually |
|---|
| J 0.65 16.5 | for smoke and displays the current levels. K 0.98 25 |
|---|
| L 0.25 6.4 | Reset: Resets all the alarms and faults on the detector and EQUAL M 0.06 1.6 N 0.91 23 its associated displays. If the alarm or fault condition has (4) “L” DIA. O 1.0 26 not been cleared then the appropriate fault indications will MOUNTING |
|---|
| HOLES | be repeated. Reset does not clear the isolate mode. Isolate: Isolates the detector from any external devices or systems. This includes all the relays in the detector and (2) “L” DIA. in remote units. Isolate relay is activated while the detector ANCHOR |
|---|
| M | is in isolate mode EQUAL HOLES Fault Indicators: System: A fault that affects the whole VESDA system (any devices connected on VESDAnet) |
|---|
| FRONT VIEW | SIDE VIEW Zone: A fault that affects only the assigned VESDA detector and its associated displays. Urgent: A serious fault that requires immediate attention. 19" Sub Rack This light will only illuminate when at least one other fault light is lit. Power: A fault with either the mains AC or battery backup power supply. |
|---|
| 尺寸 | Network: A failure in the VESDAnet communications link. |
|---|
| in mm | Airflow: Airflow drift. Urgent indicates serious aspirator or A 19 482 |
|---|
| B | 5 128 pipe failure. |
|---|
| C 4.75 120 | Filter: Filter needs replacing. Urgent indicates that filter D 0.82 21 E 3.82 97.2 replacement is overdue. F 0.25 6.4 |
|---|
| G 0.62 16 | Ordering Information TOP VIEW |
|---|
| H 0.56 14 | Display, in Remote Mounting Box with termination card: I 7.50 190 |
|---|
| J 1.4 36 | LaserPLUS 7 Relays VRT-200 |
|---|
| K 0.28 7 | LaserPLUS No Relays VRT-600 |
|---|
| L 0.39 10 | LaserFOCUS 7 Relays VRT-V00 M 0.31 8 |
|---|
| N 17.37 440 | LaserSCANNER 7 Relays VRT-400 |
|---|
| O | 4 102 LaserSCANNER 12 Relays VRT-800 (TYP.) P 4 98.5 LaserSCANNER No Relays VRT-700 |
|---|
| LaserCOMPACT | 7 Relays VRT-J00 |
|---|
| Recessed Mounting Kit (Optional) | VSP-012 |
|---|
| Doc. no. 13803_08 | Part: 17921 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 |
|---|
| GF13803_08 page 2 of 2 | www.gamewell-fci.com |
|---|