| UI x 2 | • Resistive Temperature Sensor |
|---|
| Power Characteristics | Input — NTC10K Type II, C7021 series — NTC10K Type III (Space Tem- Table 1. Power Characteristics perature Sensor only), C7023 series |
|---|
| 供電 | Rated voltage: 24VAC — NTC20K, TR21, and C7041 50/60Hz, series |
|---|
| Working voltage range: | • Temperature Accuracy 20-30VAC, UL listed — ±1°F(±0.5°C) at 50 to 90 °F(10 |
|---|
| class-2 transformer or IEC | to 32°C) 61558 listed transformer. — ±2°F(±1.1°C) at 30 to 122°F(- 1.1 to 50°C) |
|---|
| 功耗 | Max. 8.5VA @ 24VAC • Voltage Input, SELV (Display ON) (355mA @ 24VAC) — 0-10V, ±5% of full scale |
|---|
| Min. Load | 4VA (all DOs OFF, No Sylk • Digital Input |
|---|
| sensor) | — Dry contact closure — Open circuit (≥ 100Kohms) |
|---|
| Max. Load | 96VA (all DOs ON) — Closed circuit (≤100ohms) |
|---|
| DO (G, | • Relay Output |
|---|
| Display | Y1,Y2,Y3,W1,W2 ,W3) • Rated Average Current — 1A at 24VAC • Rated Pulse Current |
|---|
| Table 2. Display | — 3.5A at 24VAC |
|---|
| Display Type | 24 BPP TFT display with DO (AUX) • Relay Dry Contact |
|---|
| CTP | • Rated Average Current — 1A at 24VAC/DC |
|---|
| Resolutions | 480x480 pixel • Rated Pulse Current — 3.5A at 24VAC/DC |
|---|
| Active Display Area | 4” diagonally |
|---|
| Backlight | LCD (Dimmable) Operating Environment Table 4. Operating Environment |
|---|
| Ambient | 32 to 122 °F (0 to 50°C) |
|---|
| Table 3. IO Characteristics | Operating Temperature |
|---|
| UIO x 2 | • Resistive Temperature Sensor |
|---|
| Input | Ambient 10 to 90% relative humidity (non- |
|---|
| — NTC10K Type II, C7021 series | Operating condensing) |
|---|
| — NTC10K Type III (Space Tem- | Humidity perature Sensor only), C7023 |
|---|
| series | Storage -40 to 150 °F(-40 to 65.5°C) |
|---|
| — NTC20K, TR21, and C7041 | Temperature series |
|---|
| • Temperature Accuracy | Protection IP20 |
|---|
| — ±1°F(±0.5°C) at 50 to 90 °F(10 | Class to 32°C) — ±2°F(±1.1°C) at 30 to 122°F(- 1.1 to 50°C) Onboard Sensors • Voltage Input, SELV |
|---|
| — 0-10V, ±5% of full scale | Table 5. Onboard Sensors • Digital Input |
|---|
| — Dry contact closure | Temperature Heat: 40 to 90°F (4.5 to 32°C) |
|---|
| — Open circuit (≥ 100Kohms) | Cool: 50 to 99°F (10 to 37°C) |
|---|
| — Closed circuit (≤100ohms) | Resolution: 1 °F (0.5°C) |
|---|
| • Voltage Output | Control Accuracy: ±1.5°F (0.8°C) at |
|---|
| — 0-10V, ±3% of full scale @2K | Room Temperature ohms |
|---|
| Humidity | Range: 20~90% RH Resolution: 1%RH Control Accuracy: ±5%RH at Room Temperature and 20~90%RH |
|---|
| Compliances | Table 9. Supported Sensors and Functions |
|---|
| Sensors | Options Part Numbers Table 6. Compliances |
|---|
| Dirty Filter | Direct DPS200, DPS400, |
|---|
| Certificates | CE, FCC, ICES, UL/cUL, RoHs, REACH, Sensor (Normally Open) DPS1000 |
|---|
| California Title 24, BTL, and Prop65. | Reverse (Dry contact (Normally differential |
|---|
| Standards | EN 60730-1, EN 60730-2-9, EN Closed) pressure switch) 301489-1, EN 301489-17, EN 300328, EN 301893, EN 62479, Proof Of Air Direct DPS200, DPS400, |
|---|
| UL60730-1, UL60730-2-9, Title 47 | Flow Sensor (Normally Open) DPS1000 |
|---|
| part 15 subpart B, Title 47 part 15 | Reverse (Dry contact |
|---|
| subpart C, RSS 210, ICES-003 | (Normally airflow switch) Closed) |
|---|
| Communication Technologies | Shutdown Direct Dry contact |
|---|
| Sensor | (Normally Open) shutdown switch |
|---|
| Table 7. Communication Technologies | Reverse (Normally |
|---|
| BACnet IP | Over Wi-Fi Closed) |
|---|
| WiFi | 802.11 b/g/n Mixed Air NTC 20K C7250A, C7041 |
|---|
| Supported security levels | Temperature NTC 10K Type II C7021 |
|---|
| OPEN, | Sensor NTC 10K Type III C7023 |
|---|
| WPA, | Sylk C7400S WPA2, WPA3_WPA2_AES |
|---|
| Outdoor Air | NTC 20K C7250A, C7041 |
|---|
| 藍牙 | BLE 4.2 with 1 Mbps Temperature NTC 10K Type II C7021 |
|---|
| Classic Bluetooth with | Sensor NTC 10K Type III C7023 |
|---|
| max. 3 Mbps | Sylk C7400S |
|---|
| SylkTM | Honeywell SylkTM Return Air NTC 20K C7250A, C7041 |
|---|
| Temperature | NTC 10K Type II C7021 |
|---|
| BACnet MS/TP | Over RS485 Sensor NTC 10K Type III C7023 (9.6, 19.2, 38.4, 76.8, Sylk C7400S 115.2 Kbps) |
|---|
| Discharge Air | NTC 20K C7250A, C7041 |
|---|
| Electrical Characteristics | Sensor NTC 10K Type III Sylk C7023 C7400S |
|---|
| Table 8. Electrical Characteristics | Space NTC 20K TR21, C7041, |
|---|
| Rated Impulse Voltage | 500 V Sensors NTC 10K Type III C7772F, C7023, |
|---|
| Sylk | C7772G |
|---|
| Construction of Control | Independently Mounted TR40, TR40-H, |
|---|
| Control | TR40-CO2, TR40- H-CO2 |
|---|
| 操作方式 | Type 1 Action TR120 (max 1) |
|---|
| Pollution Degree | 2 CO2 sensor 0-10 / 2-10 VDC C7233, C7263, |
|---|
| Purpose of Control | Operating Control TR40-CO2 TR40-H-CO2 |
|---|
| Supported Sensors and Functions | Proof of Digital Input Dry contact |
|---|
| waterflow | waterflow switch Table 9. Supported Sensors and Functions |
|---|
| Window Open | Direct Dry contact |
|---|
| Reverse | sensor |
|---|
| Occupancy | Direct Dry contact (Normally |
|---|
| Table 9. Supported Sensors and Functions | Table 10. Terminal Identification |
|---|
| Drain Pan / | Direct Dry contact BACnet Communications |
|---|
| Leak Detector | (Normally Open) float switch or (BACnet MS/TP A) |
|---|
| Closed | (BACnet MS/TP B) Jumper between R and RC for R-RC |
|---|
| Terminal Identification | single transformer system 24VAC power from cooling transformer |
|---|
| G | Fan Relay output, Compressor contactor (stage1) Relay output, Compressor contactor (stage2) 24VAC Relay output, Compressor |
|---|
| Y3 | contactor (stage3)/Configurable Output |
|---|
| W1 | Relay output, Heat (stage1) |
|---|
| W2 | Relay output, Heat (stage2) |
|---|
| Fig. 1. Terminals | Relay output, heat (stage3)/Configurable Output Table 10. Terminal Identification Relay dry contact, Aux-1 |
|---|
| Terminal | Label Connection Aux 24VAC power from heating Relay dry contact, Aux-2 transformer 24VAC 24VAC common (Neutral). For 2 |
|---|
| transformer systems, use | Thermostat Variants common wire from cooling |
|---|
| transformer | Table 11. Thermostat Part Numbers 1 Universal input/output TC500A-N Thermostat with North |
|---|
| UIO1 | American Wi-Fi |
|---|
| COM | Common conformance 2 Universal input/output UIO2 |
|---|
| UI2 | 3011-7144-001 Replacement Backplate |
|---|
| 類型 | Terminal Label |
|---|
| DEFAULT | INPUTS OUTPUTS |
|---|
| DO1 | G Supply Fan Fan Command High Speed Fan |
|---|
| DO2 | W1 Heat Stage 1 Heating Floating Open |
|---|
| DO3 | W2 Heat Stage 2 Heating Floating Closed |
|---|
| DO4 | W3 / Aux NA Heat Stage 3, Cool/Compressor Stage 4, Reversing Valve OB, Low Speed Fan, Medium Speed Fan, Occupancy, Dehumidification, Humidification, Purge Output, Exhaust Fan 1, Exhaust Fan 2. |
|---|
| DO5 | Y1 Cool/Compressor Cooling Floating Open Stage 1 |
|---|
| Digital | DO6 Y2 Cool/Compressor NA Cooling Floating |
|---|
| Outputs | Stage 2 Closed |
|---|
| DO7 | Y3 / Aux NA Cool/Compressor Stage 3, External Economizer, Low Speed Fan, Medium Speed Fan, Occupancy, Dehumidification, Humidification, Purge Output, Exhaust Fan 1, Exhaust Fan 2. |
|---|
| DO8 | Aux Cool/Compressor (Dry Contact, Stage 4, 2 terminals) External Economizer, Low Speed Fan, Medium Speed Fan, Occupancy, Dehumidification, Humidification, Purge Output, Exhaust Fan 1, Exhaust Fan 2. 5 31-00398M-06 | Rev. 02-23 Table 13. Terminal Assignments Terminal Assignments (Default & Optional Assignments) |
|---|
| UI1 | UI1 NA CO2 Sensor Input, (2 terminals) Dirty Filter, Universal Discharge Air Sensor, |
|---|
| Inputs | UI2 UI2 NA Drain Pan Sensor, (2 terminals) External Economizer Fault, Mixed Air Sensor, |
|---|
| Proof of Airflow, | Modulating Cool, |
|---|
| Universal | UIO2 UIO2 NA Modulating Heat, |
|---|
| Inputs/ | Proof of Waterflow, (2 terminals) Return Air Sensor, Purge Output. Outputs Shutdown, Space Temperature Sensor, Window Open Sensor. |
|---|
| R | R 24v Power |
|---|
| RC | RC 24v Power / Cooling 1 Selectable type pre- |
|---|
| Sylk Bus | S-Bus Sylk connection defined by Sylk address 2 number 4 x 11/32” 3 -19/32 ” (91.2 mm) (9mm) 4 x 3/16” (4.5mm) 4 - 15/32” 2 - 3/8” 3 - 1/4” (113.7 mm) (60.3mm) (82.75mm) 7 - 2/25 ” (180 mm) 2/5” (10.2 mm) 5 - 9/10” (150 mm) 7 31-00398M-06 | Rev. 02-23 |
|---|
| GENERAL SAFETY | applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions |
|---|
| INFORMATION | suivantes: 1. L’appareil ne doit pas produire de brouillage; start-up), all manufacturer instructions and in trique subi, même si le brouillage est susceptible particular the mounting Instructions guide (31- d’en compromettre le fonctionnement. 00399M) and the user guide (31-00400M) are to be • This equipment has been tested and found to comply |
|---|
| observed. | with the limits for a Class B digital device, pursuant to |
|---|
| only by authorized and trained personnel. | provide reasonable protection against harmful |
|---|
| followed. | equipment generates uses and can radiate radio by the manufacturer, all warranties concerning accordance with the instructions, may cause harmful |
|---|
| operation and safety are invalidated. | interference to radio communications. However, there |
|---|
| observed at all times. | particular installation. If this equipment does cause |
|---|
| has been approved by Honeywell. | which can be determined by turning the equipment off temperature for at least 24 hours before applying interference by one or more of the following measures: power. This is to allow any condensation resulting from — Reorient or relocate the receiving antenna. low shipping/storage temperatures to evaporate. — Increase the separation between the equipment 60730-1, and UL60730-2-9. — Connect the equi |
|---|
| user-serviceable parts inside! | technician for help. 2014/35/EU and EMC Directive 2014/30/EU. separation distance of 20 cm or more should be |
|---|
| complies with Canadian ICES-003. | compliance, operations at closer than this distance is Operation is subject to the following two conditions: (1) • Les antennes installées doivent être situées de facon à This device may not cause harmful interference, and (2) ce que la population ne puisse y être exposée à une this device must accept any interference received, distance de moin de 20 cm. Installer les antennes de including interfe |
|---|
| operation. | cm ou moins de la position centrale de l’ antenne. expressly approved by the party responsible for • Limited by local law regulations, version for North compliance could void the user's authority to operate America does not have region selection option. the equipment. |
|---|
| • This device contains licence-exempt | Safety Information as per EN60730-1 transmitter(s)/receiver(s) that comply with Innovation, TC500A-N Thermostat is intended for residential, Science and Economic Development Canada’s licence- commercial environments. exempt RSS(s). Operation is subject to the following |
|---|
| two conditions: | TC500A-N Thermostat is an independently mounted 1. This device may not cause interference. electronic control system with fixed wiring. 2. This device must accept any interference, including interference that may cause undesired operation of TC500A-N Thermostat is used for the purpose of building |
|---|
| the device. | HVAC control and is suitable for use only in non-safety le présent appareil est conforme aux CNR d’Innovation, Sciences et Développement économique Canada Note All images used in this document are for illustrative purposes only and may not match the actual product. ® U.S. Registered Trademark |
|---|
| customer.honeywell.com | © 2023 Honeywell International Inc. 31-00398M-06 | Rev. 02-23 |
|---|