| Valve Type: Control Ball Valve | 3-way ball valve, A-B-AB flow, full or reduced port using patented flow control insert. |
|---|
| Body Pattern: 2-way, 3-way | Internal NPT connections. Body Pressure Rating (maximum): Glycol. Not for use with steam or fuels. Medium Temperature Range: for 3-way A port and ANSI Class III seat leakage specification (0.1% of CV) for 3-way B port Flow Characteristics: 2-way:Equal Percentage with flow control insert. +121°F) Compatible Actuators: |
|---|
| Materials: | Minimum Torque Required: |
|---|
| Body: Brass | 35 lb-in. (4 Nm) up to 3 in. (.DN80) |
|---|
| Ball and Stem: | 27 lb-in. (3 Nm) up to 1-1/4 in. (.DN32) Two-way: Nickel-chrome plated brass or 316 Stainless Fail Safe: MSXX05* |
|---|
| Steel. | Non-Fail Safe: MVN* and MNXX05* |
|---|
| Three-way: Nickel-chrome plated brass. | * These actuators are available as factory installed |
|---|
| Seat: Teflon® seals with EPDM O-rings | assemblies. See Table 1 for all available options. Approvals/Standards: |
|---|
| Body Style: | Valves: ANSI Class IV close-off/leakage (maximum 0.01% |
|---|
| port using patented flow control insert. | Actuators: See literature for the given actuator. 1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care 1985 Douglas Drive North Golden Valley, Minnesota 55422-4386 3. http://customer.honeywell.com or http://customer.honeywell.ca Table 1. VBN Model Selection Table. Model Selection: Ball Valve Body/ Flow Ty |
|---|
| Actuator | Fail Position Accessories |
|---|
| VB - ball valve | MVN613A0000*** (Leave blank) = Fail in (Leave blank) |
|---|
| N- Female NPT threaded | MVN613L0000*** place = No Cable C1 = 2 - 2-way MVN643A0000*** 1 m cable 3 - 3-way MVN643L0000*** C3 = 3 m cable MVN713A0000*** MVN713L0000*** |
|---|
| A---1/2 (DN15) | MN6105A1011 (Leave blank) |
|---|
| B---3/4 (DN20) | MN6105A1201 = No enclosure |
|---|
| C---1 (DN25) | 3R = |
|---|
| D---1-1/4 (DN32) | MN7505A2001 NEMA 3R |
|---|
| E---1-1/2 (DN40) | MN7505A2209 Enclosure F---2 (DN50) |
|---|
| G---2-1/2 (DN65) | MS7505A2030 FSO = Fail Safe Open |
|---|
| H---3 (DN80) (VBN2) | MS7505A2130 (VBN2) FSC = Fail Safe Closed |
|---|
| xxx.xx - CV Designator See Table 4 | MS8105A1030 (VBN2) |
|---|
| and 5. | MS8105A1130 FSA = Fail A-AB Open (VBN3) |
|---|
| P - Plated Brass | MS4105A1030 FSB = Fail B-AB Open |
|---|
| S - Stainless Steel | MS4105A1130 (VBN3) (VBN2) |
|---|
| A* - Standard Base | MS7103A2021*** (Leave blank) |
|---|
| L** - Low Profile | MS7103A2221*** = 3 ft cable |
|---|
| X - MN/MS DCA | standard |
|---|
| Actuator Bracket | MS3103A1023*** MS3103A1223*** MS7503A2021*** MS7503A2221*** |
|---|
| VB N | 2 A 004.70 P A + MVN613A0000 + + C1 3 63-2648—09 Table 2. Actuator Control Description. |
|---|
| MVN613A0000 | Floating, Two-position (SPDT) (90 sec. timing), 24 V, Fail in Place |
|---|
| MVN643A0000 | Floating, Two-position (SPDT or SPST) Fast Acting (30 sec. timing), 24 V, Fail in Place |
|---|
| MVN713A0000 | 0(2)-10 Vdc Modulating, 24 V, Fail in Place |
|---|
| MN6105A1011 | Floating, Two-position (SPDT), 24 V, Fail in Place |
|---|
| MN6105A1201 | Floating, Two-Position (SPDT), 24 V, Fail in Place with end switches |
|---|
| MN7505A2001 | 0(2)-10 Vdc Modulating, 24 V, Fail in Place |
|---|
| MN7505A2209 | 0(2)-10 Vdc Modulating, 24 V, Fail in Place with end switches |
|---|
| MS7505A2030 | Universal, 0(2)-10 Vdc Modulating, Floating, Two-position (SPDT), 24 V, Fail Safe |
|---|
| MS7505A2130 | Universal, 0(2)-10 Vdc Modulating, Floating, Two-Position (SPDT), 24 V, Fail Safe with end switches |
|---|
| MS8105A1030 | Two-Position (SPST), 24 V, Fail Safe |
|---|
| MS8105A1130 | Two-Position (SPST), 24 V, Fail Safe with end switches |
|---|
| MS4105A1030 | Two-Position (SPST), 120 V, Fail Safe |
|---|
| MS4105A1130 | Two-Position (SPST), 120 V, Fail Safe with end switches |
|---|
| MS7103A2021 | 2-10 Vdc Modulating, 24 V, Fail Safe |
|---|
| MS7103A2221 | 2-10 Vdc Modulating, 24 V, Fail Safe with end switches |
|---|
| MS3103A1023 | Sylk-enabled, 24 V, Fail Safe |
|---|
| MS3103A1223 | Sylk-enabled, 24 V, Fail Safe with end switches |
|---|
| MS7503A2021 | Universal, 0(2)-10 Vdc Modulating, Floating, Two-Position, 24 V, Fail Safe |
|---|
| MS7503A2221 | Universal, 0(2)-10 Vdc Modulating, Floating, Two-Position, 24 V, Fail Safe with end switches Table 3. Control Ball Valve Short Order Codes ½” – 3”. Model Selection: Ball Valve Body Flow Valve Size Actuator Adapter Valve Type Trim |
|---|
| VBN - Control Ball Valve | 0 - No Actuator (valve only) 0 - No Actuator 00 - None 2 - 2-way 1 - 24 Vac, Floating, 90 sec. or Fail in Place 00 - None 3 - 3-way (MVN613, Fail in place)*** (FIP) 01 - C1 - 1 m 2 - 24 Vac, Floating/2-Pos., 30 sec. Cable (MVN643, Fail in place)*** 03 - C3 - 3 m Cable 3 - 24 Vac, Modulating 0(2)-10 Vdc (MVN713, Fail in place)*** 4 - 24 Vac, Floating/2-Position 00 - None (MN6105, Fail in place) 02 |
|---|
| Vdc/Floating, 2-Position | Safe Open (FSO) (MS7505, Fail safe) 2 - VBN2 Fail 7 - 24 Vac, 2-Position (MS8105, Safe Closed |
|---|
| Fail safe) | (FSC) 3 - VBN3 Fail 8 - 100-250 Vac, 2-Position Safe A to AB (MS4105, Fail safe) Open (FSA) 9 - 100-250 Vac, 2-Pos. w/ end 4 - VBN3 Fail |
|---|
| switches (MS4105, Fail safe) | Safe B to AB Open (FSB) |
|---|
| CV Designator. | A - 24 Vac, 2-Position w/ end |
|---|
| Options range from B-2. | switches (MS8105, Fail safe) |
|---|
| See Table 4 and 5. | B - 24 Vac, Mod 0(2)-10 Vdc/ Floating/ 2-Position w/ end switches (MS7505, Fail safe) |
|---|
| P - Nickel Chrome | E - 24 Vac, Mod. 2-10 Vdc 01 - 3 ft Cable |
|---|
| Plated Brass | (MS7103, Fail safe)*** |
|---|
| S - 316 Stainless Steel | F - 24 Vac, Mod. 2-10 Vdc w/ end (VBN2) switches (MS7103, Fail safe)*** |
|---|
| VBN | 2 A B P A 1 0 00 5 63-2648—09 Table 4. Cv Designator for Two-Way VBN Ball Valves. Valve |
|---|
| Body | Size B D E F G H J K L M N P R S T U 1 2 |
|---|
| VBN2A 1/2” | 0.38 0.68 1.3 2.0 2.6 4.7 11.7* |
|---|
| VBN2B 3/4” | 4.3 7.4 10.1 29* |
|---|
| VBN2C 1” | 9.0 15.3 26 54* |
|---|
| VBN2D 1-1/4” | 14.9 25 37 102* |
|---|
| VBN2E 1-1/2” | 41 74 172* |
|---|
| VBN2F 2” | 42 57 71 100 266* |
|---|
| VBN2G 2-1/2” | 72 101 202* |
|---|
| VBN2H 3” | 124 145* Table 5. Cv Designator for Three-Way VBN Ball Valves. Valve |
|---|
| VBN3A 1/2” | 0.33 0.59 1.0 2.4 4.3 8.0 |
|---|
| VBN3B 3/4” | 3.8 7.0 11.0* |
|---|
| VBN3C 1” | 8.6 14.9 22 31 |
|---|
| VBN3D 1-1/4” | 12.7 19.4* 27 34* |
|---|
| VBN3E 1-1/2” | 24 32* 61 |
|---|
| VBN3F 2” | 38 57 83 109 |
|---|
| VBN3G 2-1/2” | 74 100* |
|---|
| MVN Actuator | SPECIFICATIONS Actuator Type: Valve Rotational Stroke: 90° ±3°. Fail Safe Mode: Non-spring return, Fail in place Torque: 27 lb-in. (3 Nm). External Auxiliary Switches Available: No Supply Voltage: 24 Vac +20%, -15%, 24 Vdc Power Consumption: 5 VA- Modulating; 1.5 VA - Floating; 6 VA - Fast Acting SPDT Environmental Rating: NEMA2 Frequency: 50 Hz; 60 Hz |
|---|
| APPLICATION | Mounting: Click-on installation – no tool required Noise Rating at 1m (Maximum): 35 dB(A) max at 1 m Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Ambient Temperature Range: -4°F to 131°F |
|---|
| FEATURES | (-20°C to 55°C) Storage Temperature Range: -40°F to 176°F (-40°C to 80°C) Weight: See Table 7 (2-way) and Table 8 (3-way) Dimensions: See Fig. 4-6, Table 7 (2-way) and Table 8 (3- 1/2 to 1-1/4 inches. Electrical Connections: Field wiring 18 to 20 AWG to screw positions. Humidity Ratings: 5% to 95% RH non-condensing. Design Life (at Rated Voltage): 60,000 cycles; 1 cycle = 0°…90°…0° Cable Specifica |
|---|
| I | 1 m or 3 m length available. Environmental Protection Ratings: IP40 Approvals: UL/cUL; UL60730 |
|---|
| CLEARANCE ABOVE ACTUATOR 3/4 (19) | Table 6. Actuators and Accessories. |
|---|
| L | C3- 3 meter MVN643A0000 Fast acting SPDT contol ball valve actuator cable MVN643L0000 Fast acting SPDT contol ball valve actuator MVN713A0000 Modulating control ball valve actuator |
|---|
| A | MVN713L0000 Modulating control ball valve actuator To order actuator with accessories order actuator part |
|---|
| MVN WITH 2-WAY BALL VALVE | M34956 number + accessory. For example: MVN613A0000 + C1 Fig. 1. MVN with 2-way ball valve. See Table 4. 7 63-2648—09 |
|---|
| Non-Spring Return Direct Coupled | Frequency: 50 Hz; 60 Hz |
|---|
| • Adjustable mechanical end limits | Canadian Underwriters Laboratories, Inc.: cUL C22.2 No. 24-93 (22 to 14 AWG) for electrical connections 1-5/8 cable (MN7505) or floating/2-position control (MN6105) 3-11/32 (85) |
|---|
| SPECIFICATIONS | 5-9/32 4-1/4 (108) (134) |
|---|
| Torque: 44 lb-in. (5 Nm) | 2-7/16 2-19/32 (62) (66) M23103A |
|---|
| Environmental Rating: NEMA2 | Fig. 2. Non-spring return direct coupled actuator dimensions diagram. |
|---|
| Spring Return 3 Nm Diamond | Cable Specification: Power Cable: Plenum Rated, 3 ft (0.914 m) length from end of access cover, 18 AWG Switch Cable: Appliance Rated, 3 ft (0.914 m) length from end of access cover, 18 AWG Ingress Protection Rating: IP54 Environmental Rating: NEMA 2 Frequency: 50 Hz; 60 Hz Mounting: Direct Coupled Maximum Noise Rating, Driving (dBA @ 1m): < 40 Maximum Noise Rating, Spring Return (dBA @ 1m): < 65 R |
|---|
| 防護等級 | UL60730 |
|---|
| range of shaft sizes | UL1097 for Double Insulation CE Certification Low Voltage Directive 2014/35/EU |
|---|
| • Fast test mode | CE EMC 2004/108/EC 2-7/8 (73) (40) limits 6-1/2 5-3/8 (178) (137) |
|---|
| Spring Return Torque: 27 lb-in (3 Nm) | 3-17/64 (83) |
|---|
| FOR 1/2 INCH SHAFT. | M37351 Fig. 3. Dimensions in in. (mm). 9 63-2648—09 |
|---|
| Spring Return Direct Coupled | Spring Return Direction: By orientation |
|---|
| protection on all models | Directive 2006/95/EC; IEC 60730-1 and Part 2-14 C-Tick: N314 |
|---|
| • UL (cUL) listed and CE compliant | 4-9/16 (116) 6-61/64 (177) 5-27/32 (148) |
|---|
| Fail Safe Mode: Spring Return | 2-1/64 (55) M27712A Fig. 4. Spring return direct coupled actuator dimensions |
|---|
| Spring Return Torque: 44 lb-in. (5 Nm) | diagram. |
|---|
| B | E D |
|---|
| C | M34950 Fig. 5. 2-way ball valve dimensions for models with MN and MS actuators. See Table 7. |
|---|
| E | D |
|---|
| K | K |
|---|
| L STANDARD BASE = 3-7/8 (98) | A |
|---|
| L LOW PROFILE = 3-1/4 (82) | H |
|---|
| Pipe Size | Dimensions in in. (mm) (valve Replacement |
|---|
| CV | J J only) Stem |
|---|
| In. | (DN) Code Designators A B C D E Fmsa Fmnb H I (w/std) (w/low) K lbs. Assembly** 2.00, 2.60, 4.70, (60) (87) (168) (76) (102) (206) (175) (116) (71) (139) 13/16 (41) 5112-22 (SS) 11.70* (123) (60) (87) (164) (76) (102) (206) (175) (139) 13/16 (41) (123) 10.10, 29.00* 2-5/8 3-11/16 6-1/2 3 4 8-5/16 7-1/16 5-5/8 5 (127) 1- 1 (67) (94) (165) (76) (102) (211) (180) (143) 13/16 (45) (95) (94) (179) (76) |
|---|
| J | J only) Stem |
|---|
| In. (DN) Code CV Designators | A B C D E Fmsa Fmnb G H I (w/ std) (w/ low) K lbs. Assembly 2.40, 4.30, 8.00 (89) (84) (76) (102) (238) (206) (60) 9/16 13/16 (170) (154) (72) 11.00* (71) (84) (165) (76) (102) (224) (192) (156) (140) (58) (97) (173) (76) (102) (249) (217) (67) (181) (165) (83) 14.90, 31.00 4-5/16 4 (102) 7-13/16 3 4 10- 9-9/16 3-1/4 8-1/8 7-1/2 4-5/16 3.3 (114) (198) (76) (102) 13/16 (243) (83) (206) (191) (109) |
|---|
| Rangeability | 41 17 52 * 321 159 251 |
|---|
| Cv | 72.00 101.00 202.00 |
|---|
| VBN2G | Rangeability 287 558 877 |
|---|
| VBN2H | Rangeability 750 877 13 63-2648—09 |
|---|
| Effective CV | Table 11. Effective CVs Using Pipe Reducers (Three-way) |
|---|
| Size | Pipe Size (NPT) (in.) 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" |
|---|
| Effective CVa | 0.33 0.33 0.30 0.30 |
|---|
| a Multiply the C | S.I. (metric) units are required. v value by 0.865 to get the capacity in kvs, if S.I. (metric) units are required. 100% Valve sizing is important for correct system operation. 80% Undersized valves do not have sufficient capacity at FULL PORT maximum load. Oversized valves do not have sufficient FLOW authority over the load in modulating applications. 60% Oversized valves can cause excessive cycl |
|---|
| opening. | 2-WAY CHARACTERIZED FLOW |
|---|
| Proper Use | 20% |
|---|
| direct coupled actuators only. | Fig. 8. Typical characterized VBN2 flow. 80% |
|---|
| IMPORTANT | 3-WAY VALVE The presence of excessive iron oxide (red rust) in B PORT FLOW |
|---|
| the system voids the valve warranty. | 60% FLOW 40% 20% Table 12. Close-off, Differential Pressure Ratings. 0° 30° 60° 90° Close-off |
|---|
| VALVE STEM STROKE | M29525 |
|---|
| Valve | Pressure Rating |
|---|
| 類型 | Valve Size (in.) (psid) Fig. 9. Typical characterized VBN3 flow. 1, 1-1/4, 1-1/2, 2, 2-1/2, 3 100 600 WOG PRESSURE/TEMPERATURE CHART 1-1/4, 1-1/2, 2, 2-1/2 40 600 |
|---|
| NOTE: | 3-way close-off ratings apply to 3-way valves |
|---|
| with the B port plugged | 500 400 |
|---|
| Flow Characteristics, Fig. 8, 9 | PRESSURE (PSI) 300 characterized flow control insert. 100 |
|---|
| The VBN3 Three-Way Ball Valves have: | 0 0 100 200 300 400 characteristic. 20% reduced Cv. The valve body is rated for WOG (water, oil, and gas), but the valve with its internal components are only rated for water and not for oil or gas. 15 63-2648—09 |
|---|
| Cavitation Limits | Ball Valve to provide optional 316 stainless steel ball and stem for 2- ΔP < 1/2 x (absolute head pressure (psia) - water way valves. Valve shall have a blow-out proof stem with two vapor pressure (psia)) EPDM O-rings with minimum 600 psi rating. Valve stem polymer ball insert to make flow control equal percentage. |
|---|
| balancing valve. | 35 lb-in. torque for 1/2 to 3 in. sizes. Valve shall be available with a minimum of 32 unique CV values. Valve shall be available with threaded (FNPT) end connections. |
|---|
| TYPICAL SPECIFICATIONS | The 3-way valves shall be installed in a “T” configuration with actuator perpendicular to shaft. Valve shall not require elbows of any kind. The 3-way valves shall have EPDM O- |
|---|
| Valve Actuator | rings behind ball seals to allow for a minimum close-off pressure of 40 psi with an actuator that provides 35 lb-in. Table 13. Actuator Accessories and Replacement Parts. Couple Actuators MVN613A0000 MVN643A0000 MVN713A0000 MVN613L0000 MVN643L0000 MVN713L0000 MN Non-Fail- Direct Couple MS Fail-Safe Safe Direct Actuators |
|---|
| Part Number | Description |
|---|
| MVNAAA | Replacement Valve Adaptor x x x |
|---|
| MVNAAL | Replacement Valve Adaptor, Low Profile x x x |
|---|
| MVNAC7131 | Replacement Cable with Terminal 1m, x x Modulation (RED, BLACK, WHITE) |
|---|
| MVNAC6131 | Replacement Cable with Terminal 1m, Floating x x x x (RED, BLACK, WHITE) |
|---|
| MVNAT3 | Replacement Screw type Terminal Block, x x x x x x Pluggable to 2-10 Vdc |
|---|
| Q7002B1009 | Universal Interface Module x x |
|---|
| STRN-SCSA | Self-centering Shaft Adapter x |
|---|
| STRN-STRNRLF | Stain Relief Fitting (10 pack) x 17 63-2648—09 |
|---|
| When installing this product... | Refer to actuator literature for actuator dimensions. 1. Read these instructions carefully. Failure to follow 1. Clean the lines upstream of particles larger than |
|---|
| them could damage the product or cause a | 1/16 in. diameter (welding slag, pipe scale and other |
|---|
| hazardous condition. | contaminants). 2. Check ratings given in instructions and on the 2. Proceed with installation once the system specifics product to ensure the product is suitable for your (expansion/contraction of the system and its |
|---|
| application. | medium as well as operating pressures) are within 3. Installer must be a trained, experienced service tolerances. |
|---|
| technician. | 3. Eliminate air from system. 4. After installation is complete, check out product 4. Two-way valves are marked to show flow direction. operation as provided in these instructions. IMPORTANT Flow arrows must point in the direction of the flow |
|---|
| Preparation | for proper operation. NOTE: For three-way valve mounting, see Fig. 11 and 12. CAUTION Equipment Damage Hazard 5. Stem rotation: a. For two-way valves: Foreign particles like dirt and metal chips can (1) Clockwise to close. |
|---|
| damage the ball seals. | (2) Counterclockwise to open. b. For three-way valves: For trouble-free operation of the product, good (1) Clockwise to increase B to AB flow. installation practice must include initial system (2) Counter clockwise to increase A to AB flow. flushing, and chemical water treatment. Clean the lines upstream of particles larger than 1/16 inch NOTE: After valves have been installed in the piping, the d |
|---|
| Remove all filters before flushing. | of the notch indicates the flow through the ball (i.e. when the notch is parallel to the axis of the valve Do not use boiler additives, solder flux and wetted between A and B ports, the ball will allow flow materials which are petroleum based or contain through the valve). For three-way valves, the flow mineral oil, hydrocarbons, or ethylene glycol acetate. can be determined by the orientation of |
|---|
| Mechanical Installation | SUPPLY |
|---|
| AB PORT | A PORT COIL AB PORT RETURN A PORT COIL Hold valve with pipe wrench by hexagonal fitting B PORT B PORT |
|---|
| RETURN | SUPPLY ONLY. Do NOT handle the valve body with the pipe |
|---|
| wrench; product damage may result. | DIVERTING MIXING M13737 (not to scale). |
|---|
| FLOW | FLOW 2-WAY; OPEN 2-WAY; CLOSED 3-WAY; A-AB OPEN 3-WAY; B-AB OPEN M34954 FULLY COUNTER CLOCKWISE AS SHOWN. FOR 2-WAY VALVES TO MOUNT ACTUATOR ON CLOSED VALVE, TURN ACTUATOR FULLY CLOCKWISE AS SHOWN. FOR 3-WAY VALVES TO MOUNT ACTUATOR ON A-AB VALVE, TURN ACTUATOR Fig. 14. Vertical valve installation. FULLY COUNTER CLOCKWISE AS SHOWN. FOR 3-WAY VALVES TO MOUNT ACTUATOR ON B-AB VALVE, TURN ACTUATOR FU |
|---|
| COUPLER** | M29519A ANTI-ROTATION |
|---|
| BRACKET** | Fig. 16. Acceptable valve angle from vertical for MN and MS actuators. MOUNTING |
|---|
| PLATE** | Mounting Plate Adjustment The Actuator Mounting Plate can be rotated to a different position for installation in confined spaces. This is WING NUT** accomplished as follows: STEM RETAINER PLATE 1. Remove the handle from the shaft and set it aside. 2. Remove the two screws that hold the stem assembly to the mounting plate and set them aside. VALVE BODY 3. Remove and set aside the stem assembly. 4. |
|---|
| Electrical Installation | 2 3 4 CONTROLLER 1. If necessary, remove actuator wiring cover. 2. Wire actuator using Fig. 17 through 41 for the appli- cation required. 3. Replace cover. 1 24 VAC 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS |
|---|
| FLOATING ACTUATOR | AND OVERLOAD PROTECTION AS REQUIRED. M18946A DIRECT SERVICE/OFF Fig. 18. MN6105 with Floating Control. REVERSE PROPORTIONAL ACTUATOR 2 -10 Vdc 0 -10 Vdc 0 -10 Vdc 2 -10 Vdc CONTROLLER 2 3 4 FEEDBACK 1 1 2 3 4 5 24 VAC 3 PROPORTIONAL CONTROLLER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 24 VAC |
|---|
| PROTECTION AS REQUIRED. | FEEDBACK 2 CONNECTION REQUIRED FOR SPST CONTROL. |
|---|
| M34869A | + |
|---|
| Fig. 17. MN6105 with On/Off SPDT Control. | – 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 0(2)-10 VDC OF 0(4)-20 mA CONTROL SIGNAL ACCEPTABLE. SET CONTROL SIGNAL DIP SWITCH TO “OFF” FOR VOLTAGE. |
|---|
| SET TO “ON” FOR CURRENT. | M18947B Fig. 19. MN7505 with 0(2)-10 Vdc Control. FLOATING ACTUATOR |
|---|
| END SWITCHES (CLASS II-ONLY) | 1 BLACK 5° 85° WHITE 24 VAC BROWN SPST 2 3 4 |
|---|
| S1 | S2 S3 S5 S6 M25214A 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. |
|---|
| aux./end switches. | Fig. 23. MVN643 with Two Position SPST Control. PROPORTIONAL/MODULATING: 4-20mA CONTROLLER OUTPUT WITH |
|---|
| BLACK | PROPORTIONAL ACTUATOR 24 VAC DIP SWITCH POSITION 2 1 2 MODE WHITE |
|---|
| OFF | OFF 2-10V |
|---|
| BROWN | ON OFF 10-2V |
|---|
| ON | ON 10-0V RED |
|---|
| MINIMUM | CONTROLLER |
|---|
| Fig. 21. MVN613 with Floating Control. | + |
|---|
| CLASS 2 | ACTUATOR |
|---|
| PROPORTIONAL ACTUATOR | 1 RED 1 24 VAC |
|---|
| DIP SWITCH POSITION | 2 V 1 2 MODE 2 BLACK |
|---|
| + | 10-2 VDC |
|---|
| WHITE | 3 0-10 VDC |
|---|
| – | FLOATING, REV 0 (2)-10 VDC 1 LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS |
|---|
| CONTROLLER | AND OVERLOAD PROTECTION AS REQUIRED. 1 2 3 2 24 VDC SUPPLY ACCEPTABLE. 3 SET SWITCH TO MODULATING IF AVAILABLE. M37320 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD |
|---|
| RED | 2 BLACK 1 24 VAC V |
|---|
| PROPORTIONING | 4 BROWN |
|---|
| BROWN 90°-0°/FEEDBACK | MINIMUM |
|---|
| SPDT | – 2-10 VDC |
|---|
| PROVIDE DISCONNECT MEANS AND | 10-0 VDC FLOATING, REV |
|---|
| OVERLOAD PROTECTION AS REQUIRED. | FLOATING, FWD 1 LINE VOLTAGE POWER SUPPLY. |
|---|
| FLOATING, REV | PROVIDE DISCONNECT MEANS AND 2 SET SWITCH TO FLOATING. OVERLOAD PROTECTION AS REQUIRED. M37304 2 24 VDC SUPPLY ACCEPTABLE. Fig. 26. MS7505 with Two Position SPDT Control. 3 SET SWITCH TO MODULATING IF AVAILABLE. M37321 CLASS 2 Fig. 29. MS7103 with 4-20 mA Control (MS7503 shown, ACTUATOR ignore selection switch). 1 RED 1 24 VAC V 2 BLACK 3 WHITE 0°-90°/MODULATING 4 BROWN 90°-0°/FEEDBACK 1 LINE VOLT |
|---|
| FEEDBACK | 10-0 VDC 2 24 VDC SUPPLY ACCEPTABLE. M34973 FLOATING, FWD FLOATING, REV |
|---|
| ACTUATOR | 1 1 RED 1 SPST 2 V |
|---|
| V | 2 2 BLACK 3 WHITE 0°-90°/MODULATING 4 BROWN 90°-0°/FEEDBACK ACTUATOR 1 LINE VOLTAGE POWER SUPPLY. |
|---|
| PROVIDE DISCONNECT MEANS | 1 LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS |
|---|
| AND OVERLOAD PROTECTION | 2-10 VDC AND OVERLOAD PROTECTION AS REQUIRED. |
|---|
| AS REQUIRED. | 10-2 VDC M34974 3 0-10 VDC 2 24 VDC SUPPLY ACCEPTABLE. 10-0 VDC FLOATING, FWD 3 SET SWITCH TO MODULATING FLOATING, REV Fig. 32. MS8105 with Two Position SPDT Control. IF AVAILABLE. M37322 Fig. 30. MS7103 with 2-10 Vdc Control using two ACTUATOR actuators (MS7503 shown, ignore selection switch). 1 24 VAC 2 V 3 OR + |
|---|
| CABLE | PROVIDE DISCONNECT MEANS AND 2-10 VDC |
|---|
| SPST SWITCHES | 10-2 VDC OVERLOAD PROTECTION AS REQUIRED. 3 0-10 VDC |
|---|
| BLUE | 2 24 VDC SUPPLY ACCEPTABLE. 10-0 VDC |
|---|
| SWITCHES BLACK | M34975 |
|---|
| SPST | 0-10 VDC M29122 |
|---|
| Fltg, rev | Fig. 38. MS4105 with 120 Vac Two Position SPDT 1 LINE VOLTAGE POWER SUPPLY. control. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24 VDC SUPPLY ACCEPTABLE. 3 SET SWITCH TO MODULATING. M19577A Fig. 35. MS7505 with override to full closed. ACTUATOR 1 24 VAC V 2 S3 S2 S1 3 OR + 0/2 TO 10 VDC M35813 |
|---|
| Fltg, fwd | 1 24 VAC ACTUATOR Fltg, rev 2 1 1 LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS V |
|---|
| AND OVERLOAD PROTECTION AS REQUIRED. | 2 1 24 VAC 3 OR + 2 24 VDC SUPPLY ACCEPTABLE. 0/2 TO 10 VDC 4 OR N/A 3 SET SWITCH TO MODULATING. M34976 PROPORTIONING |
|---|
| COM | 3 0-10 VDC 10-0 VDC |
|---|
| OHMS, | 2 CONTROLLER 1/2 W 5 FEEDBACK 3 OR + MINIMUM 2-10 VDC 4 OR N/A |
|---|
| M34977 | Fig. 40. MS7505 with 0(2)-10 Vdc controller operating multiple actuators. Fig. 37. MS7505 with 4-20mA Controllers. 3. If the control scheme requires fail-safe operation, ensure that, upon removal of power, the fail position |
|---|
| HOT | BROWN S-BUS wrench. COM b. Loosen all other mounting bolts connecting the |
|---|
| S-BUS | actuator to the mounting bracket, and set aside. |
|---|
| AND OVERLOAD | ADDRESS 14 of the actuator, as displayed in Fig. 42. |
|---|
| Fig. 41. MS3103 with Sylk Bus control. | side of the actuator, aligning it based on the stroke labelling. aluminum valve stem coupler are included in using the groove of the coupling. |
|---|
| Replacement Kit (part no. 5112-11). | e. Reconnect the actuator to the valve mounting bracket by replacing the screws previously removed (step b) |
|---|
| OPERATION AND CHECKOUT | f. Tighten the shaft coupling bolt using a 10 mm wrench. 1. Cycle the actuator to verify that the direction of rota- tion suits the control sequence. 2. If the rotation direction is incorrect: a. For 2-position and Sylk-enabled actuators: Remount actuator on the bracket. b. For floating control actuators: Reverse two control signal wires (CW/CCW). c. For analog control actuators either: (1) Reposi |
|---|
| reverse/direct acting switch 1. | M19579A Fig. 42. Mounting shaft coupling to actuator opposite side. 25 63-2648—09 ® U.S. Registered Trademark |
|---|