| Version 7.0 | Page 39 of 54 a. The B578 learns the IP Address of where TermDMS is running and what Deep Mesh Domain is being used and initiates a connection to TermDMS to “report in”. b. TermDMS will look at the Edge Router ID of the reporting device to determine if this is the first time it has seen this particular device. If so, it will send a request to the device to send its configuration information to Ter |
|---|
| POSITION/COLOR/STATE | MEANING |
|---|
| Left-Yellow LED OFF | 10 Mbs connection |
|---|
| Left-Yellow LED ON | 100 Mbs connection |
|---|
| Right-Green LED Blinking | Network connection active D3 and D4 LED Key for B578 Loaded with B578_X_V1_06.srec or later version (X=L,S or R) |
|---|
| B578-L | B578-S B578-R D3 Red , D4 Yellow alternately blink for 5 Power was just applied to the B578-L Power was just applied to the B578-S Power was just applied to the B578-R seconds D3 Red randomly blinks , D4 Yellow Rapid Yellow D4 rapid blink indicates the B578-L has Yellow D4 rapid blink indicates the B578-S has Yellow D4 rapid blink indicates the B578-R has |
|---|
| steady blink (5 blinks / second) | connected to TermDMS. Red D3 LED blinks connected to TermDMS. Red D3 LED blinks connected to TermDMS. Red D3 LED blinks anytime a connected Room Gateway sends data. anytime a connected Room Gateway sends anytime a connected Room Gateway sends |
|---|
| data. | data. D3 Red and D4 Yellow are OFF and never The B578-L is not powered , not loaded with The B578-S is not powered , not loaded with The B578-R is not powered , not loaded with |
|---|
| blinking | software or is damaged. Verify the B578 is software or is damaged. Verify the B578 is software or is damaged. Verify the B578 is powered via 12VDC via 12V power socket or via powered via 12VDC via 12V power socket or via powered via 12VDC via 12V power socket or via |
|---|
| PoE network switch | PoE network switch PoE network switch D3 Red OFF , D4 Yellow repeating ON for This is a B578-L that is powered but has not yet N/A N/A 2 seconds and OFF for 2 seconds connected to TermDMS |
|---|
| D3 Red ON for 1 second,Off for 1 second | N/A This is a B578-S that is powered but has not yet |
|---|
| and repeats. D4 Yellow Blinks 2 times | been configured with an Encryption Key. It can't |
|---|
| every 2 seconds | connect to TermDMS until it gets configured with its Encryption Key via DM_Workbench or EngINN |
|---|
| and repeats. D4 Yellow Blinks 3 times | been configured with an Encryption Key. It can't |
|---|
| D3 Red OFF. D4 Yellow Blinks 2 times | N/A This is a B578-S that is powered but has not yet |
|---|
| D3 Red OFF. D4 Yellow Blinks 3 times | N/A N/A This is a B578-R that is powered but has not yet |
|---|
| D3 Red OFF. D4 Yellow ON solid | N/A The B578-S is in Ready to Teach mode. For the The B578-R is in Ready to Teach mode. For the Encrypted B578-S, you must first place it in Encrypted B578-R, you must first place it in Ready to Teach mode by pressing the blue S1 Ready to Teach mode by pressing the blue S1 button before sending its configuration from button before sending its configuration from |
|---|
| DM_Workbench or EngINN | DM_Workbench or EngINN D3 and D4 LED Key for B578 Loaded with B578_X_V1_05.srec or previous version (X=L,S or R) |
|---|
| yet connected to TermDMS | yet connected to TermDMS |
|---|
| D3 Red OFF. D4 Yellow ON Solid | N/A This is a B578-S that is powered but has not yet This is a B578-R that is powered but has not yet been configured with an Encryption Key. It can't been configured with an Encryption Key. It can't connect to TermDMS until it gets configured with connect to TermDMS until it gets configured with |
|---|
| its Encryption Key via DM_Workbench or | its Encryption Key via DM_Workbench or |
|---|
| EngINN. | EngINN |
|---|
| D3 Red ON Solid. D4 Yellow ON Solid | The B578-L was loaded with the B578-L The B578-S was loaded with the B578-S The B578-R was loaded with the B578-R "AutoConfig" file setting the B578 type to B578-L "AutoConfig" file setting the B578 type to B578-S "AutoConfig" file setting the B578 type to B578-R , but it was not programmed with the actual , but it was not programmed with the actual , but it was not programmed with the actual oper |
|---|
| Customer Service. | Customer Service. Customer Service. |
|---|
| Mode | Peak Current Consumption |
|---|
| B578 logic board (basic) | 200mA peak, 100mA RMS The B578 can be powered via PoE (Power over Ethernet), or locally from an external 12VDC power source PoE Powered B578 The B578 is an IEEE 802.3af compliant Powered Device (PD) interface with a current mode switching regulator. The B578 is an IEEE class 2 device. PoE devices are classified below. |
|---|
| IEEE Class | Minimum Power Output at the Maximum Power Input at the |
|---|
| PSE | Powered Device 0 15.4W 0.44 to 12.95W 1 4.0W 0.44 to 3.84W 2 7.0W 3.84 to 6.49W 3 15.4W 6.49 to 12.95W If the B578 exceeds its IEEE 802.3af class-2 power rating (i.e., draws more than 7W), the PoE switch in the network will shut down the power and Ethernet connectivity to the B578. For B578 to support PoE power, order the PoE module (02-9949). Connect the module to M1 header on the B578 logic boar |
|---|
| Pin 2 – 12VDC | Pin 3,4,5 – Not used and you should not connect anything to these pins Two cables are available that can plug into H2: 62-2035 – 3 Pin to 3 Pin 300mm . Brown wire Pin 1 - Common, Red wire Pin 2 - 12VDC 62-1511-A0 – 5 pin 300mm with stripped ends. Brown wire Pin 1-Common, Red wire Pin 2 -12VDC Cut/Remove un-used wires from the cable |
|---|