| SPECIFICATIONS | Bulb: UVL-32-LAMP: 33.75 in (857 mm) length UVL-60-LAMP: 61.25 in (1156 mm) length UV-C Power: |
|---|
| when properly positioned | UVL-60-LAMP: 54 W |
|---|
| EPA Est. No. 075179-FL-2 | UVL-32-LAMP: 250 μW/cm2 |
|---|
| Electrical Ratings: | UVL-60-LAMP: 395 μW/cm2 |
|---|
| Power Rating: 120-277 Vac, 50/60 Hz | Spectrum: |
|---|
| Temperature Ratings: | Bulb Type: |
|---|
| 尺寸 | Bulb Life: |
|---|
| Power Supply: 13.0 in x 3.75 in x 2.5 in | 18,000 hours (330 mm x 95.3 mm x 63.5 mm) Accessories: UVL-32-LAMP 32 inch replacement lamp UVL-60-LAMP 60 inch replacement lamp Table 1. Models. |
|---|
| Part Number | Description Replacement Lamp(s) Power Supply* UVL-32-LAMP |
|---|
| UVL-COIL-32S | RTU / AHU 32" Single Bulb (MFG# TUVCPS-HS) (MFR# TUVCL-232HO) UVL-32-LAMP (2) |
|---|
| UVL-COIL-32D | RTU / AHU 32" Double Bulb (MFG# TUVCPS-H32D) (MFR# TUVCL-232HO) UVL-60-LAMP |
|---|
| UVL-COIL-60S | RTU / AHU 60" Single Bulb (MFG# TUVCPS-HS) (MFR# TUVCL-260HO) UVL-60-LAMP (2) |
|---|
| UVL-COIL-60D | RTU / AHU 60" Double Bulb (MFG# TUVCPS-H46-60D) (MFR# TUVCL-260HO) |
|---|
| PLANNING THE | A |
|---|
| 安裝 | B D |
|---|
| H | J L WARNING |
|---|
| WARNING | E Only qualified technicians should install this |
|---|
| product. | C Install in accordance with relevant building codes. F I Read instructions carefully including safety warnings. |
|---|
| E. 1/2” Pipe Straps | Fig. 1. Parts System Configuration Determine the dimensions of the coil to be irradiated. Use |
|---|
| H. L - Mounting Brackets | Table 2 To determine which kit is needed based on the coil size. Table 3 can be used to estimate the kits needed based |
|---|
| I. Black Nylon Zip-Ties | on the tonnage of the unit. The coil size should be verified to insure proper fit. Before attaching the L-brackets for mounting use optimal |
|---|
| K. Sight Glass | irradiation distance (Fig. 2.) and lamp spacing (Fig. 3.) |
|---|
| required depending on configuration) | be positioned properly. The UV lamps are mounted onto a framework of EMT tubing. When two or more UV lamps are supported on a single length of EMT it is recommended to add an optional vertical support. (Fig. 4.) Table 2. Sizing Based on Coil Dimensions. Coil Width (inches) 32 40 48 56 62 72 24 UVL-COIL-32S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32S UVL-COIL-32D UVL-COIL-60S Coil Height (inches) 32 UVL |
|---|
| Fig. 2. Optimal Irradiation Distance. | exceed 12 inches. • The distance of UV lamp ends to the edge of irradiated surface should not exceed 10 inches. • The spacing guidelines above may not apply for all applications. Use recommendations in Table 2 to select 12” Max. space between lamps appropriate kit based on coil size. 10” Max. space to end of coils Overlap lamps where necessary WARNING Be careful of damage to equipment. Ultraviolet |
|---|
| Fig. 3. Lamp Spacing. | structure of plastic material found in HVAC equipment, avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation. WARNING UV Light Hazard. Harmful to bare skin and eyes. Can cause temporary or permanent loss of vision. Do not look at the UV lamp when lighting is on. Use indicator light on the ballast to check status. In order to prevent expos |
|---|
| When Installing This Product… | the vertical support to the floor and ceiling for a snug fit. (Fig. 7.) them could damage the product or cause a hazard- ous condition. product to make sure the product is suitable for your 1/2” Pipe Coupling application. nician. operation as provided in these instructions. |
|---|
| Assemble Conduit Framework | Vertical Support duit/lamp clamps (Fig. 5.), do not fully tighten bolts yet. 1/2” Pipe Coupling Fig. 7. Optional Vertical Support. Install UV Lamps |
|---|
| Fig. 5. Slide on Hardware. | Snap UV Lamps into the lamp/conduit clamps. Be sure to clamp to the rubber lamp connector on one end and the air handler wall or supporting structure. Then use the lamp glass. Use black nylon zip-ties to secure lamp cables ½ inch pip clamps to attach the tubing sections to to tubular rack components and/or supports. the L-Brackets. (Fig. 6.) CAUTION Breakable Glass Hazard. Can cause personal injur |
|---|
| Conduit | MERCURY NOTICE This device contains mercury in the sealed ultraviolet bulb(s). Do not place your used bulb(s) in the trash. Dispose of properly. Broken Bulb Cleanup Do not use a household vacuum. Sweep debris into a |
|---|
| Fig. 6. Mount L-bracket and Tubing. | plastic bag and dispose of properly. conduit tubing to support framework and prevents instructions regarding recycling and the proper disposal of sagging on installations with three or more lamps per old bulb(s). 5 31-00402—02 UV LAMP UV LAMP CONNECTORS |
|---|
| UV Lamp | L1 BLACK |
|---|
| L2 or N WHITE | 120-277 VAC POWER SUPPLY GND GREEN Fig. 8. Installing UV Lamp. |
|---|
| Mount Power Supply(s) | Fig. 10. Electrical Connections. power supplies, and cables are in place join the lamp and Align Pins & Lamp Key |
|---|
| Sight Glass Installation | Lamp Key Power Supply |
|---|
| Push Firmly Together | Cable Fig. 11. Align Pins and Lamp Key. |
|---|
| Fig. 9. Sight Glass Installation. | MAINTENANCE Honeywell UVC lights are made of Hard Quartz. Unlike Soft |
|---|
| WIRING | Quartz, these lamps do NOT need to be wiped of grease or other contaminants, and are NOT affected by humidity. They are warranted for 2 years of UVC output, to 60% of their original output. Sizing guidelines are based on the |
|---|
| Can cause personal injury. | Honeywell UV lamps are rated for two years germicidal Turn off main power before making electrical effectiveness. The visible blue light will continue to |
|---|
| connections. | illuminate, but does NOT have any germicidal effectiveness. Bulbs must be replaced on schedule for the IMPORTANT Use only Honeywell replacement lamps. Use of replacement lamps from other manufacturers voids the warranty. See Table 1 for replacement lamp part numbers. Table 4. Troubleshooting. |
|---|
| Problem | Solution |
|---|
| UV Lamp(s) Not Lighting | 1. Check that power is applied. 2. Check that the unit is turned ON. 3. Ensure the remote lamp cables are properly connected. 4. Check the fuse. Replace only with same size and type. 5. Reset power switch on power supply (off then on). 6. Install New UV Lamp(s). 7. Consult Factory. |
|---|
| UV Lamp(s) Flickering | 1. UV Lamp(s) have reached end of effective service life. Install new lamp(s) of same type. 2. If unit is new, check remote cables to ensure they are properly con- nected. 3. Reset power switch on power supply (off then on). 4. If new lamps still flicker, consult factory. |
|---|
| UV Lamps Have burned Out Prematurely | 1. Consult Factory. |
|---|
| Power Supply Will Not Light UV Lamps even | 1. Consult Factory. |
|---|
| after new lamps are installed | 2. External power suppressor may be needed if power surges occur. 7 31-00402—02 ® U.S. Registered Trademark |
|---|