| Panels. | Operation Dialer Capture Module returns a handshake to the fire panel. |
|---|
| Features | The fire panel then sends the contact ID reports to the Dialer Capture Module, which in turn sends a kiss-off after the report is |
|---|
| tomer's shared IP equipment is required. | Module sends the contact ID reports over the ECP bus to the dual GSM technology as back-up. GSM path utilizes GPRS the fire panel goes on-hook. The iGSM communications module and automatically switches to SMS if GPRS is unavailable. then transmits the messages to the central station (either over configuration. The IPGSM-COM connects directly to the pri- |
|---|
| mary and secondary telephone ports. | Easy to Program There are two ways to configure the IPGSM-COM communica- 100Base network connection (LAN or WAN), DSL modem or tor panel: cable modem. 1. Handheld programmer 7720P secured with the industry's advanced encryption standard 2. Web-Based Programming - Allows complete interactive (AES 256 bit). programming from AlarmNet Direct. https://services.alarmnet.com/AlarmNetDirect |
|---|
| IP addressing. | The IPGSM-COM Communicator can be pre-programmed. Use the 7720P programmer or the Web-Based Program to enter all central-station information. This is saved to the IPGSM-COM design accommodates back-up battery. Includes primary communicator panel memory. When the IPGSM-COM Commu- power and battery supervision. nicator is installed at the site and connected to the Internet/ information including whe |
|---|
| Panel Capabilities | • Dimensions: 15.625" H x 13.79" W x 9.25" D (39.7 cm H x 34.9 cm W x 23.9 cm D) |
|---|
| described in the SIA DC-05 standard. | Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 – |
|---|
| AlarmNet | 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non- condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful board, transformer, manual, and required screws, cables, etc. |
|---|
| Installation Requirements | GSM-ANT3DB: 3db gain external/remote antenna 7626-50HC: 50 ft. antenna cable, low loss 7626-25HC: 25 ft. antenna cable, low loss WA7626-CA: SNA to N Adapter within 20 feet of host Fire Alarm Control Panel sounder, or 7720P: IPGSM-COM handheld programmer |
|---|
| other remote sounder. | HPTCOVER: Plug in transformer box for IPGSM communicator facility power source branch as the host Fire Alarm Control |
|---|
| Panel. | Agency Listings and Approvals |
|---|
| backup capability. | The listings and approvals below apply to the basic IPGSM- COM communicator panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in |
|---|
| Electrical Specifications | process. Consult factory for latest listing status. |
|---|
| • Transformer: | • UL: S789 |
|---|
| – Primary: 120 VAC, 60 Hz, 0.50 A. | • CSFM: 7300-1645:0183 – Secondary: 18VDC, 50 VA. – PowerBoost1 power supply: 90mA Standby, 90 mA Active – iGSM Communications Module: 80mA Standby, 500mA Active (peak during transmission) – Dialer Capture Module: 40mA Standby, 85mA Active – LED Display board: 10mA Standby, 10mA Active – TOTAL: 220mA Standby, 685mA Active (IPGSM-COM cabinet holds one 7.0 AH battery.) Fire•Lite® is a registered tra |
|---|