| supports 70.7 volt speaker devices. | • ECC-50/100C can be controlled by an FACP via the ANN/ To add more control and increase system capacity, any com- ACS (EIA-485) link. Compatible FACPs include the MS- |
|---|
| ECC-LOC). | • Certified for seismic applications when used with the appro- priate seismic mounting kit • Integral supervised microphone |
|---|
| greater than 1,000 occupants. | grammed time • 14 recorded messages • Field-selectable message and custom message recording |
|---|
| ule replacement | • External Audio Input can be used for background music DF-60815:B • 7/28/2015 — Page 1 of 6 types AC fail reporting of AC Loss – AC Power Loss Relay - TB1 – System Trouble Relay - TB2 – MNS Active - TB3 for addressable modules when interfaced with compatible addressable FACPs and End-of-Line power supervision relays product manual LS10001-000FL-E) soles: – Optional ECC-LOC Local operator console |
|---|
| amplifier. | Control and Indicators PUSH BUTTON CONTROLS |
|---|
| • System Control | • Trouble Silence |
|---|
| board by two metal brackets. | • Speaker Select 1-24 • Console Lamp Test |
|---|
| NAC Circuit | Speaker Circuits |
|---|
| TB19 | TB20 & TB21 |
|---|
| ECC-50W-25/70V | ECC-CE6 circuit expander FIRE SYSTEM optional amplifier |
|---|
| ALL | ACTIVE SYSTEM |
|---|
| CALL | CONTROL options FIRE SYSTEM |
|---|
| FI | LIT AL TB4 by Honeywell TB12 |
|---|
| external battery | TB22 charger - J7 CHG-120F charger ECC-50/100C Emergency Command Center (Possible Configurations) Canadian DF-60815:B • 7/28/2015 — Page 3 of 6 |
|---|
| LED Status Indicators (visible with | BAT-12120: Battery,12 volt,12.0 AH (Two required). |
|---|
| door closed) | BAT-12180: Battery,12 volt, 18.0 AH (Two required). |
|---|
| Fire System Active (green) | LOC/RM 1-8 Active (green) Wiring Requirements |
|---|
| MNS Control (green) | Main Console Fault (yellow) See product manual, part number LS10001-000FL-E for |
|---|
| System Control (green) | AC Power (green) detailed wiring requirements. |
|---|
| System in Use (green) | Ground Fault (yellow) Total System Capacity: (ECC-50/100C |
|---|
| Charger Fault (yellow) | only) |
|---|
| Speaker Zone 1-24 Fault | • Total Built-in Audio Power: 50 Watts. Battery Fault (yellow) |
|---|
| OK to Page (green) | Data Bus Fault (yellow) • Total Built-in Speaker Circuits: 2. |
|---|
| Microphone Trouble (yellow) | NAC Fault (yellow) • Total Expandable Speaker Circuits: 8. |
|---|
| Message 1-8 Active (red) | NAC Active (green) |
|---|
| • | Audio Message Max Time Duration: 60 seconds. |
|---|
| Message 1-8 Fault (yellow) | System Trouble (yellow) |
|---|
| Remote Amplifier 1-8 Fault | Electrical Specifications Audio Riser Fault (yellow) |
|---|
| LOC/RM 1-8 Fault (yellow) | PRIMARY (AC) POWER (TB15) ECC-50/100C: 120 VAC, 60 Hz, 3.5 amps (HOT, NEU). |
|---|
| LED Indicators (visible with door and | Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation. |
|---|
| dress panel open) | SECONDARY POWER (BATTERY) CHARGING CIR- |
|---|
| • Speaker Volume Control Fault (yellow). | CUIT (J7) |
|---|
| • Option Card Fault (yellow). | • Supports lead-acid batteries only. |
|---|
| • Amplifier Over Current Fault (yellow). | • Float charge voltage at 27.3V • Maximum charge current: 1.0 Amp |
|---|
| Product Line Information | • Maximum battery charge capability: 2.8 Amps, 26AH (ECC |
|---|
| recordable messages. | AC LOSS RELAY CONTACT RATING (TB3) |
|---|
| SPECIAL | APPLICATION POWER (AUX. POWER) • NAC Reverse Polarity Current (requires End-of-Line Resis- |
|---|
| • 500 mA @ 24 VDC | • Contact Closure Operation Current (requires 4.7KΩ, ½ watt End-of-Line Resistor P/N 27072): 6.6 mA maximum |
|---|
| End-of-Line power supervision relays | • Maximum Wiring Impedance CMD1 - CMD8 (Contact Clo- sure Operation): 200Ω CMD1and CMD2 will be programmed for Reverse Polarity only. |
|---|
| SPEAKER VOLUME CONTROL OVERRIDE (TB23) | See manual P/N: LS10001-000FL-E for more details. |
|---|
| for Class B operation | • Operation current: 3.8 mA, maximum |
|---|
| Speaker Circuits | • Minimum isolation withstand voltage: 1500 VRMS |
|---|
| • Primary Speaker Circuit (TB20) | EXTERNAL OPERATOR INTERFACE POWER OUTPUT only) • Non-resettable power for external operator interface com- |
|---|
| – Circuit can be wired Class B or Class A | ponents |
|---|
| – Power-limited circuitry | • Power-limited circuitry, non-supervised – Normal Operating Voltage: 25 VRMS @ 2 amps max and • Nominal operating voltage: 24 VDC maximum Load Impedance of 12.5Ω (70.7 VRMS @ 700 • Maximum output current: 0.80 amps mA max. with maximum load Impedance of 100Ω opera- tion possible by plugging optional ECC-XRM-70V conver- • Current limit: fuse-less, electronic, power-limited circuit sion transformer |
|---|
| µF | • Maximum wiring impedance: 13.2Ω. – End-of-Line Resistor required for Class B circuit: 15 KΩ, 1 FACP DATA BUS (EIA-485) (TB13) watt (P/N: ELR-15K) • Dedicated connection to FACP serial bus • Output terminals: pass-through to other system components. • Isolated, supervised • Minimum isolation withstand voltage: 1500 VRMS • Maximum wiring impedance: 40Ω (ANN-BUS), 26Ω (ACS-BUS) |
|---|
| tact closure only. | • Frequency range: 400 Hz - 4 KHz RMS |
|---|
| B or Class A) | • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seis- @ 2.0 amps max. (Maximum Load Impedance of 12.5Ω) ance of 100Ω operation possible for the primary circuit by plugging in an optional ECC-XRM-70V conversion trans- former into J12 of the main control board. The same opera- tion is possible for the optional 50W amplifier by selecting the ECC-50W-70V model ground music, and alarm 4,000Hz capac |
|---|
| system requirements. | of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www. |
|---|