| www.gamewell-fci.com | GF15211-16 Rev. A page 1 of 2 On the Imager, a termination card provides all field wiring terminals, and DIP switches enable the user to configure the detector for particular applications. Supply Voltage Alignment of the Emitter is simply achieved using a laser alignment tool to rotate the 20 to 30 VDC (24 VDC nominal) optical spheres until the laser beam projected from the alignment to |
|---|
| Imager. | Nominal (at 24 VDC): The Imager is aligned in a similar way so that its Field of View (FOV) encompasses all 4 mA (1 Emitter) Emitters. A Trouble or Fault will be indicated if an Emitter is missing or outside the 7 mA (7 Emitters) |
|---|
| Imager field of view. | Peak (at 24 VDC) during training mode: 27 mA The OSID system is highly tolerant to dust and dirt and requires little maintenance in Emitter Current Consumption practice. Preventative maintenance is limited to occasionally cleaning the optical faces Wired Version (at 24 VDC): 350 μA |
|---|
| of the detector components. | Battery Version: Built-in 5 Year Battery |
|---|
| | Field Wiring OSID systems may be configured to suit a range of detection spaces by selecting the Cable Gauge number of Emitters and type of Imager. Each type of Imager differs by the lens used 0.2 - 4 mm² (26-12 AWG) in the unit, which determines the field of view and range of the system. |
|---|
| Field of View | Detection Range Max. Alarm Threshold Levels: |
|---|
| Number | Low - Highest sensitivity / earliest alarm: 20% |
|---|
| Imager | Standard Power High Power of |
|---|
| Horizontal | Vertical (0.97 dB) |
|---|
| Min | Max Min Max Emitters Medium - Medium sensitivity: 35% (1.87 dB) 10° 7° 4° 98 ft. (30 m) 492 ft. (150 m) -- -- 1 High - Lowest sensitivity / maximum immunity 45° 38° 19° 49 ft. (15 m) 197 ft. (60 m) 98 ft. (30 m) 393 ft. (120 m) 7 to nuisance smoke conditions: 50% (3.01 dB) 90° 80° 48° 20 ft. (6 m) ** 111 ft. (34 m) 39 ft. (12 m) ** 223 ft. (68 m) 7 Adjustment Angle ±60° (horizontal) ** Maximum Dis |
|---|
| Emitter / Imager Dimensions | Dimensions (WHD) Emitter / Imager: 7.80 in. x 5.12 in. x 3.78 in. (198 mm x 130 mm x 96 mm) Operating Conditions* Temperature: 14 °F to 131 °F (-10 °C to 55 °C)* Humidity: 10 to 95% RH (non-condensing) 3OHDVHFRQVXOW\RXU;WUDOLVRI¿FHIRURSHUDWLRQ RXWVLGHWKHVHSDUDPHWHUV IP Rating IP 44 for Electronics IP 66 for Optics Enclosure Status LEDs |
|---|
| Ordering Codes | Fire Alarm (Red) |
|---|
| OSI-10 | Imager - 7º coverage OSE-SP Emitter - Standard Power Trouble / Power (Bi-color Yellow / Green) |
|---|
| OSI-45 | Imager - 38º coverage OSE-SPW Emitter - Standard Power, Wired Approvals Compliance |
|---|
| OSI-90 | Imager - 80º coverage OSE-HPW Emitter - High Power, Wired |
|---|
| OSID-INST | OSID Installation Kit Please refer to the Product Guide for details regarding compliant design, installation and commissioning. * Product UL listed for use from 32°F to 104°F (0°C to 38°C) www.xtralis.com The Americas +1 781 740 2223 Asia +852 2916 8894 Australia and New Zealand +61 3 9936 7000 Continental Europe +32 56 24 19 51 UK and the Middle East +44 1442 242 330 The contents of this document |
|---|
| Doc. no. 19797_16 | Part No. LF29582 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 |
|---|
| GF15211-16 Rev. A page 2 of 2 | www.gamewell-fci.com |
|---|