| I300 | Isolator Module. |
|---|
| • Weight: 150 grams (5 oz.). | I300A Isolator Module, ULC listed. |
|---|
| SMB500 | Optional surface-mount backbox. |
|---|
| C304 | Addressable Control Module. |
|---|
| C304A | Addressable Control Module, ULC listed. |
|---|
| Back:(888) 388-3299. | Made in the U.S.A. DF-51339 — Page 1 of 2 |
|---|
| a monitor module to the control panel. | M301 Mini-Monitor Module does not include LED. |
|---|
| • High noise (EMI/RFI) immunity. | • Two rotary switches for direct-dial entry of Decade address (01-99). |
|---|
| M300 | M301 M302 |
|---|
| Monitor Module | Mini-Monitor Module Two-wire Conventional |
|---|
| The Fire•Lite M300 Monitor Module is | Though the Fire•Lite M301 can be used Smoke Detector |
|---|
| used with the MS-9200 to monitor a single | to monitor an entire Class B initiating cir- Monitor Module |
|---|
| open contact devices. It can be used to | N/O contact devices. The M301 is small The Fire•Lite M302 Monitor Module is |
|---|
| monitor a zone of four-wire smoke detec- | enough to fit inside a single-gang junction used with the MS-9200 to monitor a single |
|---|
| tors, manual fire alarm pull stations, | box behind the device being monitored. Its Initiating Device Circuit (IDC) of compat- |
|---|
| waterflow devices, or other normally open | small size and light weight allow it to be ible two-wire smoke detectors. The moni- |
|---|
| dry-contact alarm activation devices. The | installed without the need to be rigidly tored circuit may be wired as an NFPA |
|---|
| monitored circuit may be wired as an NFPA | mounted. It can be used to monitor a single Style B (Class B) or Style D (Class A) Ini- |
|---|
| tiating Device Circuit. | tectors, manual fire alarm pull stations, wa- external resettable 24VDC power. terflow devices (per local authority) or other normally-open, dry-contact devices. It may FEATURES |
|---|
| • Terminals with SEMS screws and clamp- | also be used to monitor normally-open su- • Supports compatible two-wire smoke de- |
|---|
| ing plates for ease of wiring. | pervisory devices with special supervisory tectors. |
|---|
| • Built-in magnetic alarm test switch. | indication at the control panel. The moni- • Supervises IDC wiring and connection |
|---|
| • Mounts in standard 4" square (2-1/8" | tored circuit/device is wired as an NFPA of external power source. |
|---|
| deep) junction boxes. | Style B (Class B) Initiating Device Circuit. • Built-in magnetic alarm test switch. |
|---|
| PRODUCT LINE | FEATURES • Mounts in standard 4" square (2-1/8" deep) junction boxes. • Compact size; only 2.75" [70 mm] high |
|---|
| module. | x 1.30" [33 mm] wide x 0.50" [12.7 mm] PRODUCT LINE |
|---|
| M300A | Contact device monitor deep. M302 Two-wire detector monitor |
|---|
| module, ULC listed. | • Tinned, stripped leads for wiring ease. module. |
|---|
| M02-04-00 | Alarm Test Magnet. • Class B (Style B) IDC only. M302A Two-wire detector monitor |
|---|
| • Capable of mounting behind monitored | module, ULC listed. |
|---|
| backbox. | device in single-gang box. M02-04-00 Alarm Test Magnet. |
|---|
| M301 | Contact device mini-monitor module. |
|---|
| M301A | Contact device mini-monitor module, ULC listed. Face plate for M300, M302, C300, and I300 |
|---|
| To a 2-wire | To MS-9200 |
|---|
| Class-B | Address- M300 and M302 |
|---|
| initiating | able |
|---|
| circuit | Loop |
|---|
| Specifications | M300 M301 M302 |
|---|
| Operating voltage: | 15 - 28VDC (peak) 15 - 28VDC (peak) 15 - 28VDC (peak) |
|---|
| Maximum current in alarm: | see MS-9200 Technical Manual see MS-9200 Technical Manual 90 mA |
|---|
| Standby current: | 400 A maximum 400 A maximum 300 A max. (Style D, 1.3 mA) |
|---|
| Temperature range: | 32 F to 120 F (0 C to 49 C) 32 F to 120 F (0 C to 49 C) 32 F to 120 F (0 C to 49 C) |
|---|
| 相對濕度 | 10% to 93% 10% to 93% 10% to 93% |
|---|
| 重量 | 150 grams (5 oz.) 150 grams (5 oz.) 150 grams (5 oz.) |
|---|
| EOL resistor value: | 47 K ohm 47 K ohm 3.9 K ohm |
|---|
| IDC loop length: | 2,500 feet (7.62 km) maximum 2,500 feet (7.62 km) maximum 2,500 feet (7.62 km) maximum |
|---|
| IDC loop resistance: | 40 ohms maximum 20 ohms maximum 25 ohms maximum |
|---|