| • Removable cover for field cleaning. | 1151 shown with 2151 shown with flangeless base. Standby current: Ion (1151): 40 µA. Photo (2151): 85 µA. Sensitivity: 1151: 1.9% ± 0.62%/ft. 2151: 3% ± 0.7%/ft. |
|---|
| CONSTRUCTION AND OPERATION | Weight: 3.6 oz. (102 g). Temperature: 32°F to 120°F (0°C to 49°C). Humidity range: 10 - 93% RH non-condensing. |
|---|
| processing to help reduce false alarms. | 2 of this document. |
|---|
| ries. | tagonal, 4" (101.6 mm) octagonal, or 4" square junction box. Bases B112LP and B116LP can utilize a single-gang, 3-1/2" |
|---|
| GENERAL SPECIFICATIONS | octagonal, 4" octagonal, 4" square, 50 mm, 60 mm, or 75 mm This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford |
|---|
| PRODUCT LINE INFORMATION | XR-2 Detector removal tool. Allows installation and/or re- |
|---|
| B100LP Series base). | XP-4 Extension pole for XR-2. Comes in three five-foot quires B100LP Series base). |
|---|
| B110LP | Base, 2-wire, low-profile flangeless, 12/24 VDC. |
|---|
| B112LP | Base, 4-wire, low-profile, Form-A & -C, 24 VDC. |
|---|
| B114LP | Base, 4-wire, low-profile, Form-A & -C + A Supervisory, 120 VAC. |
|---|
| B116LP | Base, 2-wire, low-profile, Form-C, 24 VDC. |
|---|
| RA400Z | Remote annunciator for two- or four-wire sys- tems, 3 - 32 V. Use with ion and photo plug- in detectors. Fits standard single-gang elec- trical box. |
|---|
| B401BH | Sounder base. Requires an external 24 VDC power supply. Mounts to a 4" (101.6 mm) V B110LP/RLP or B401 square electrical box (1-1/2" [38.1 mm] mini- Wiring Diagram mum depth, 2-1/8" [53.975 mm] recom- mended). |
|---|
| MOD400R | Detector sensitivity test tool. Use with most analog or digital multimeters. Satisfies NFPA 72 requirement for sensitivity testing. |
|---|
| SMK400 | Surface-mounting kit provides for entry of surface wiring conduit. Use with B401 or B401R mounting bases only. |
|---|
| A77-716B | End-of-line relay for power supervision, 12/ 24 VDC systems. V B112LP Wiring Diagram V B116LP Wiring Diagram |
|---|
| V B114LP Wiring Diagram | Base Current Alarm |
|---|
| Number | Type Resistor Type Voltage on Alarm (mA) |
|---|
| MOUNTING BASE | B110LP 2-wire* No — 12/24 VDC 10 to 100** |
|---|
| B110RLP 2-wire* | Yes — 24 VDC 22 to 62 |
|---|
| **Must be limited by control panel. | B112LP 4-wire Yes Form-A & -C 24 VDC 14 to 39 |
|---|
| B401*** | 2-wire* No — 12/24 VDC 10 to 100** |
|---|