| • | Schools • Healthcare Facilities • Factories |
|---|
| paging | Shipping Specifications ECC-50/100(E) primary operating console The listings and approvals below apply to the ECC-LOC Local |
|---|
| used for ALL CALL paging | listed by certain approval agencies or listing may be in pro- to activate all speaker circuits remotely • UL Listed S2424 • CSFM: 7300-0075 rized access. Optional thumb lock available • FDNY: COA #6152 |
|---|
| Electrical Specifications | Standards and Codes The ECC-LOC complies with the following UL Standards, |
|---|
| PRIMARY POWER REQUIREMENTS: | NFPA 72 Fire Alarm system requirements, International Build- |
|---|
| calculations. | mic). • CBC 2007 (Seismic) DF-60762:C • 7/28/2015 — Page 1 of 4 |
|---|
| ECC-50W-25/70V | ECC-CE6 |
|---|
| Internal options optional amplifier | circuit expander |
|---|
| NAC Circuit | Speaker Circuits |
|---|
| TB19 | TB20 & TB21 ECC-FFT firefighter telephone |
|---|
| remote | ECC-LOC local ECC-RPU remote |
|---|
| consoles | operator console ECC-RM remote |
|---|
| paging unit | microphone TB4 TB12 |
|---|
| external battery | distributed audio TB22 charger - J7 |
|---|
| ECC-50DA 50W | ECC-125DA 125W ECC-50BDA 50W |
|---|
| remote amplifier | remote amplifier remote amplifier |
|---|
| CHG-120F charger | CHG-75 charger ECC-50/100(E) Emergency Command Center (Possible Configurations) |
|---|
| Control and Indicators | ECC-50W-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100 power |
|---|
| PUSH BUTTON CONTROLS | output to 100 watts or can also be used as a backup amplifier. |
|---|
| DRESS PANEL OPEN) | message buttons. Please refer to the data sheet DF-60761 for more information. |
|---|
| • Option Card Fault (yellow) | ECC-RM: Remote Microphone only. Please refer to the data sheet DF-60760 for more information. ECC-50DA: Distributed (Remote) Audio Amplifier, 50 watts. Please refer to the data sheet DF-60763 for more information. |
|---|
| Information) | ECC-125DA: Distributed (Remote) Audio Amplifier, 125 watts.Please refer to the data sheet DF-60763 for more infor- |
|---|
| information. | ECC-50WBU: Expander card for ECC-BDA remote amplifier for 100 watt primary/50 watt backup operation. Please refer to DF-60762:C • 7/28/2015 — Page 3 of 4 BAT-12180: Battery,12volt, 18.0AH (Two required). |
|---|
| module. | ECC-THUMBLTCH: Optional Thumb Latch. (Non UL-listed). |
|---|
| data sheet DF-60765 for more information. | Temperature and Humidity ranges |
|---|
| FPJ-F: Remote Phone Jack. | This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non- |
|---|
| FHS-F: Fire Fighters Remote Handset. | condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this |
|---|
| MMF-300: Addressable Mini-Monitor Module. | system and its peripherals be installed in an environment with |
|---|
| I300: SLC Line Isolation Module. | a normal room temperature of 15-27º C/60-80º F. |
|---|
| ECC-LOC for seismic applications | TR-CE: Optional Trim Ring. 17.624” high (44.77 cm) x 16.0” detailed wiring requirements. Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. ©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date |
|---|