HONEYWELL HBT-BMS-W7212-W7213-W7214 安裝、保養、維修

HBT-BMS-W7212-W7213-W7214

裝ALARM | 裝防盜 | 裝警鐘 — 硬件連工程一站式

產品簡介

honeywell HBT-BMS-W7212-W7213-W7214 為Economizer Logic Modules,HKEZIT 提供原廠行貨連保養、上門安裝、調試及使用教學一站式服務。詳細規格以下方原廠 Datasheet 欄位為準,歡迎聯絡我們查詢 HBT-BMS-W7212-W7213-W7214 香港價格連安裝報價。

  • NOTES::IMPORTANT
  • —:All models include a minimum damper position All inputs and
  • DCV maximum (DCV MAX).:Humidity: 5 to 95 percent RH (noncondensing).
  • damper position setting when building is:Inputs:
  • unoccupied.:Enthalpy (C7400): 2-wire (18,20,22 AWG) connection.
HKEZIT 提供原廠行貨保養。硬件連專業安裝、設定及使用教學一站式報價,無需自行研究安裝與設定。我們同時承接裝ALARM、裝防盜、裝警鐘工程,硬件與工程同一團隊負責。
查詢價格連安裝
HBT-BMS-W7212-W7213-W7214 honeywell Economizer Logic Modules 產品圖片

詳細規格

NOTES:IMPORTANT
All models include a minimum damper position All inputs and outputs must be 24 Vac Class 2. potentiometer, and setpoints for: enthalpy or dry-bulb, occupied/unoccupied control, DCV Ambient Ratings: (CO2) operation, CO2 sensor failure mode and Temperature: -40°F to +149°F (-40°C to +65°C).
DCV maximum (DCV MAX).Humidity: 5 to 95 percent RH (noncondensing).
damper position setting when building isInputs:
unoccupied.Enthalpy (C7400): 2-wire (18,20,22 AWG) connection.
pancy, CO2 input and damper positions forMixed Air (C7150): 2-wire (18,20,22 AWG) connection. adjustments of potentiometers for MIN POS and DCV (CO2) Sensor (C7232): 0/2-10 Vdc control signal; DCV MAX. This feature was added with series 2 100K ohm input impedance. version of the product; series 1 does NOT default to DCV MAX, series 1 defaults to MIN POS on Outputs:
failure of CO2 sensor.Actuator Signal: 2-10 Vdc. Minimum Actuator Impedance: 1K ohm.
Dimensions: See Fig. 1.Exhaust Fan: Contact closure. 24 Vac Out: 25 VA maximum. 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
Approvals:3. Installer must be a trained, experienced service
Flammability Rating: UL94-5VB.4. After installation is complete, check out product
Plenum Rated.operation as provided in these instructions.
CE.5. When adding a CO2 sensor (DCV sensor) in the field,
C-tick.the MIN POS and DCV MAX position potentiometers must be adjusted by the installer. The MIN POS potenti-
Accessories:ometer must be closer to the fully CCW position that the 620 ohm, 1.2K ohm, 5.6K ohm, and 6.8K ohm checkout beteen the two settings on a call for DCV. resistors.
C7150B Mixed Air Temperature Sensor.Location and Mounting
C7232A,B Carbon Dioxide Sensors.The logic modules mount on an M7215 or a sheet metal duct
W7213 and W7214.clearance for maintenance and service (see Fig. 1 for
C7400C for use with W7212C models.dimensions). Mount device in a location protected from rain,
C7660 Dry Bulb Temperature Sensor.snow, and direct sunlight. Secure device to sheet metal using damper minimum position. control. CAUTION Equipment Damage Hazard. 4-3/8 (112) Mounting screws longer than 5/8 in. can damage internal motor components. When mounting the module to an M7215 use only the 1-5/8 included #6 5/8 in. thread-forming screw. (41) NOTE: See Fig. 4 for representative locations of connected system devices. 2-1/16
安裝5/8 INCH SCREW INCLUDED WITH LOGIC MODULE. M20717B Fig. 2. Direct mounting of module. 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3 63-2596—09 RETURN AIR SENSING 1. Ensure differential enthalpy control
OccupiedInput on Action with 24 VAC
C7400 Enthalpy Sensor andTerminal N has AQ-AQ1 power applied to W7212 24 VAC power terminalsa (TR-TR1)
Yes<1 Vdc Drives to MIN POS or DCV MAX (highest)
same for either sensor.Nob <1 Vdc Drives to DCV MAX
be of the same type.No >DCV set pt Drives to DCV MAX a <1 Vdc = no CO2 sensor or failed sensor; 1 Vdc = CO2 sen- For differential dry bulb operation use two C7650 sen- sors. Note for referential dry bulb use only the C7660 sor working but below CO2 set point and CO2 sensor work- dry bulb sensor for the most energy savings. ing and above set point. b Economizer should be powered by fan, if fan is off econo-
OUTDOOR AIR SENSINGmizer will spring return damper closed, if fan is on and no 1. Mount sensor in any orientation exposing it to freely occupancy damper will drive to DCV MAX position. circulating air while protecting it from rain, snow, and direct sunlight. 2. Connect it to the SO and SO+ terminals of the device. 1. Mount sensor in an area with unobstructed air circulation. 2. Connect it to the AQ and AQ1 terminals
DISCHARGECOMMERCIAL
AIR SENSORTHERMOSTAT
DIRECTDCV
C7046A2 C7232
EXPANSIONSENSOR COIL
W7212,C7150B
W7213,ENTHALPY 1 C7400
W7214MIXED AIR SENSOR SENSOR INDOOR FAN HONEYWELL
C7400SENSOR 1 FOR DIFFERENTIAL ENTHALPY, THE TWO C7400 ENTHALPY SENSORS ARE CONNECTED TO THE
ECONOMIZER LOGIC MODULE—ONEEXHAUST IS MOUNTED IN RETURN AIR, AND THE OTHER IS FAN MOUNTED IN OUTDOOR AIR. 2 USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR, NOT BOTH.
RETURN AIREXHAUST AIR M19547C Fig. 4. Representative locations of connected economizer system devices.
WiringOptional Applications Heat Pump Changeover
CAUTION(W7213, W7214 only) Electrical Shock or Equipment Damage Hazard. In heat pump applications, the controller must have control of
Can shock individuals or short equipmentthe changeover valve. To provide the logic module with the
circuitry.information necessary for proper information, there must be a Disconnect power supply before installation. connection to the logic module O/B terminal. This terminal alerts the logic module as to when the system operates in
IMPORTANTcooling (the only time the economizer is used). 1. All wiring must comply with applicable local codes,
ordinances and regulations.IMPORTANT 2. Refer to Table 2 for a list of the wiring diagrams and During heating applications with defrost, make sure to corresponding Figure numbers in this document. break the connection to the economizer using an iso- 3. All device inputs and outputs must be 24 Vac Class 2. lation relay. 4. Ensure proper polarity of sensor connections. Incorrect polarity negates the sensor signal. W7213 (CHAN
ActuatorEnthalpy Changeover Comments Figure Economizer
Honeywell MS7XXXSingle Single-stage cooling system. 12 W7212
Single or DifferentialTwo-stage cooling system. 13
Two-stage heat pump system.15 W7213, W7214
Honeywell M7215Single Direct mount Logic Module to Motor and 9 W7212 T7300 thermostat.
n/an/a S963 remote damper control. 6
Honeywell Series 72Single or Differential Honeywell Series 72. 14 W7212
OPERATIONWhen wired as shown in Fig. 9 through 15, the logic module responds to the cooling thermostat signal. The system uses C7400 Solid State Enthalpy Changeover Sensor(s) or C7660 at higher temperatures for free cooling when humidity is low.
setting:dry, arid climates and only in single dry bulb changeover. Do
— W7212:not use the C7660 in differential dry bulb applications. • 24 Vac (Occupied).
• No power (Unoccupied).The logic module functions as a true first stage of cooling It automatically locks out free cooling during heating; holding minimum position is defined by the potentiometers. using Demand Control Ventilation and the space CO2 level is When the module is operating in Unoccupied mode, above the set point, the damper will be between the MIN POS and there is no call for cooling, the damper drives full
INPUTSOUTPUTS
EnthalpyaCompressor N Terminalb
Demand ControlStage Stage Occupiedb Unoccupiedb
Ventilation (DCV)Outdoor Return Y1 Y2 1 2 Damper
Below setHigh Low On On On On Minimum position Closed
See Table 1 forOff Off Off Off
outdoor damperLow High On On On Off Modulatingc Modulatingc
action if input on (Free Cooling LED On)(between min. position (between closed and
AQ-AQ1 terminalsOn Off Off Off
and full-open)full-open)
This the fault forOff Off Off Off Minimum position Closed
Above setHigh Low On On On On Modulatingd Modulatingd, g
and DCV maximum)DCV maximum)
OffOff Off Off
LowHigh On On On Off Modulatinge Modulatingf (Free Cooling LED On) On Off Off Off
points and LED indications.Module follows logic detailed above.
Module follows logic detailed above.whichever is the higher of the two. When power is 24V power to B: heating mode, free cool disabled. cut to the economizer (fan is off) then the damper Actuator drives to minimum position or DCV MAX will spring return closed. whichever is the higher of the two. When power is cut to the economizer (fan is off) then the damper will spring return closed. 7 63-2596—09
SETTINGS AND ADJUSTMENTSestablished by ASHRAE standard 62.1. When used with a CO2 occupancy sensor the minimum position will modulate between the MIN POS pot setting and the DCV MAX pot setting based on the CO2 input to the AQ-AQ1 terminals from
— Exhaust setpoint.NOTES:
EXHAUSTan increased requirement for cooling, it overrides
FAN SETPOINTthe DCV maximum position potentiometer and can LED LIGHTS
N1EXH Set drive the damper full-open.
WHEN EXHAUSTN 2V 10V
P1EXH mixed air sensor overrides the DCV and closes the MINIMUM DAMPER
POSITION SETTINGP Min damper to protect from freezing the hot or chilled water coils. Control returns to normal once the Pos
MAXIMUM DAMPEROpen DEMAND CONTROL mixed air temperature rises to 48°F. Some models
VENTILATION SETPOINTDCV Max of the W7212 close the damper fully and others LED LIGHTS WHEN DEMAND CONTROL 2V 10V close the damper to minimum position. Check the label on the box for position of damper on freeze AQ1 DCV VENTILATION INPUT protection. If the CO2 sensor should fail, the
IS ABOVE SETPOINTDCV
SO+Set 2V 10V W7212 defaults to DCV maximum, providing mini- DEMAND CONTROL
Coolmum ventilation for the maximum design occu-
SRB C pancy.
LED LIGHTS WHENA D OUTDOOR AIR IS SUITABLE FOR
FREE COOLINGB
DW7212C modules have Minimum Position Adjustment the "E" enthalpy curve ENTHALPY CHANGEOVER SETPOINT
AE For detailed assistance in minimum position selection M20604B reference the Economizer Application Guide (form 63-8594) Ventilation section. The following provides basic guidelines for Fig. 5. Potentiometer and LED locations (W7212 shown). minimum position selection and adjustment: IMPORTANT
Demand Control Ventilation Setpoint• Adjust the minimum position potentiometer to allow NOTE: Make ventilation adjustments with at least a 10°F
potentiometer to be set at 6 Vdc.1. Calculate the appropriate mixed air temperature, see Equation 1. dure to adjust the damper positions for minimum OA when the space is occupied. When using a DCV sensor
Adjusting Minimum and Maximumyou will need to set the MIN POS and DCV MAX posi-
Positionstions using this procedure. DCV MAX will be the same as 4. Ensure that either the factory-installed jumper is in place will return the OA damper to minimum position (this is either across terminals P and P1 or, if remote damper position MIN POS if using a CO2 sensor or DCV MAX if a CO2 sensor is required, that it is wired according to Fig. 6 and the is NOT used). MIN POS potentiometer is turned fu
temperature reaches the calculated value.connected to one logic module. The logic module compares outdoor air to return air. NOTE: Ensure that the sensed air is well mixed. NOTE: Turn the enthalpy setpoint potentiometer fully clock- wise to the D (or E setting for W7212C) setting. 7. If all minimum (MIN POS) and maximum position (DCV MAX) adjustments are complete, remove the T-T1 The logic module selects the lower enthalpy air (return or
TO = Outdoor air temperatureExhaust Setpoint
OA = Percent of outdoor airThe exhaust setpoint determines when the exhaust fan runs
TR = Return air temperaturebased on damper position. When the exhaust fan call is made,
RA = Percent of return airthe module provides a 60 ±30 second delay before exhaust fan
TM = Resulting mixed air temperatureactivation. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.
Fahrenheit temperature.NOTES:
EXAMPLE:Assume local codes require 10% outdoor air dur- — EF and EF1 are 24V dry contacts only. An external ing occupied conditions, outdoor air is 60°F and line voltage contactor is required to operate the return air is 75°F. Under these conditions, what is exhaust fan.
the temperature of the mixed air?— When the exhaust fan is deactivated the EF and EF1 contacts open immediately. ( 0.1 × 60°F ) + ( 0.9 × 75°F ) = 6.0°F + 67.5°F = 73.5°F Adjustable Exhaust Setpoint potentiometer allows the installer to adjust the damper position need to adjust the MIN POS for the building effluent (low occupancy) airflow and adjust the DCV MAX NOTE: The 60 ±30 second delay allows the outdoor damper using the min
Enthalpy Changeover SetpointRemote Minimum Position Control Remote control of outdoor air dampers is desirable when
Outdoor Enthalpy Changeover Setpointrequiring temporary additional ventilation. The addition of a S963B1128 Remote Potentiometer allows occupants to open 9 63-2596—09 S963B1128 REMOTE POTENTIOMETER
RMINIMUM
CWP1 POSITION
CLOSEADJUSTMENT
WB ECONOMIZER M20603A Fig. 6. S963B1128 Remote Potentiometer used with logic module for remote damper control. 85 90 95 100 105 110 (29) (32) (35) (38) (41) (43) CONTROL CONTROL POINT CURVE APPROX. °F (°C)
AT 50% RH80 (27)
B70 (21) 40
C67 (19)
E55 (13) 34 D D (24) TIV (21) (18) (16) (13) B (10) C 45 D (7) (4) E 10 (2) B A D C 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 (2) (4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43) APPROXIMATE DRY BULB TEMPERATURE— °F (°C) 1 HIGH LIMIT CURVE FOR W7210D, W7212, W7213, W7214, W7340C. M23879A 11 63-2596—09
MINIMUM POSITION24 24 Vac
ADJUSTMENTVac COM
HOT24 VAC COM
C7150B MIXEDP
AIR OR C7046AT1 + –
SENSOR +SO+ 3 4
SR+EF EF1 M7215
OUTDOOR+ 3 AIR
ENTHALPY620 OHM L1
SENSORS RESISTOR (HOT) EXHAUST FAN
Y1C
Y2Y1 COOL 1
W2Y2 COOL 2
GFAN
XR L1 (HOT)
T7300/Q7300HVAC EQUIPMENT
THERMOSTATTERMINAL STRIP 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR. USE THE SAME TRANSFORMER FOR T7300 AND ECONOMIZER. 3 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-ST
OUTDOOR +5
AIR620 OHM L1
ENTHALPY SRESISTOR (HOT)
W1HEAT 1
T7350HVAC EQUIPMENT
T1+ – 2-10 VDC CONTROL
RESISTOR(HOT) SENSOR EXHAUST FAN
TB7220 OR TB8220HVAC EQUIPMENT
~1 N 2 MINIMUM POSITION
+3
FDISCHARGE T AIR SENSOR 1 2 AQ1
MS7XXX2-10 VDC –
HONEYWELLINDOOR AIR AQ
ACTUATORSENSOR + SO+ 3 4
COOL 1(HOT)
DELAYOCCUPIED RELAY
RHFDR
FDRL2
COMMERCIALHVAC EQUIPMENT
AQ12K
CONTROLCOOL 2 EXHAUST
T7300 OR T874HVAC EQUIPMENT
PROTECTION AS REQUIRED.FOR T7300, USE A1 AND A2 TERMINALS. FOR T7350 USE AUX TERMINAL. 2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA FOR TB7220 OR TB8220 USE A TERMINAL
LOAD OF THE ECONOMIZER AND ACTUATOR.THE TERMINALS ARE CONNECTED WHEN THERMOSTAT IS IN THE OCCUPIED MODE. 3 1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED 7 EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE. BY A 24 VAC INPUT. 8 SEE WIRING DIAGRAMS FIGS 9 AND 10 FOR T7350 AND TB7220/TB8220. 4 FOR T7300 ONLY 9 TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE 5 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE COMMER
TRTR1
VacCOM HOT
UNOCCUPIEDC7400 620 OHM 5 3 OUTDOOR + RESISTOR
ST6008AIR
TIMER7 ENTHALPY
L1OCCUPIED (HOT) 1 L2
AND OVERLOAD PROTECTION AS REQUIRED.EXHAUST
THE LOAD OF ALL ACTUATORS.HEAT 1
FOR T7300, USE A1 AND A2 TERMINALS.G FAN DELAY
FOR T7350 USE AUX TERMINAL.RELAY FOR TB7220 OR TB8220 USE A TERMINAL
THE TERMINALS ARE CONNECTED WHENFDR COMMERCIAL THERMOSTAT IS IN THE OCCUPIED MODE. G FAN 4 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR L2 SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY FDR 1
ENTHALPY.(HOT)
LOGIC MODULE.6 6 SEE WIRING DIAGRAMS FIGS 9 AND 10 FOR T7350 AND TB7220/TB8220. 7 TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS
ON THE COMMERCIAL THERMOSTAT.M13661B 17 63-2596—09
RCR L1 (HOT)
OO
T7300HVAC EQUIPMENT
OPTION UNDER1 W7212 SETUP” 3 “THERMOSTAT 0400 = 2 INSTALLER 3 0174 = E SETUP” 0540 = 2 0400 = 2 0174 = E HVAC EQUIP
HVAC EQUIP0540 = 2 TERMINAL STRIP TERMINAL
STRIPC 1 Y1
VISION 23 Y2 R G
PRO IAQ 3C Y2 COOL 2 RC V1 G COM
R GRH T2 FAN
COMEIM
CHECKOUT ANDW7212
TROUBLESHOOTINGN1 EXH Set
N2V 10V
checkout.T1 Pos 1 T Open DC VOLTMETER DCV CAUTION Max
Equipment Damage Hazard.AQ DCV
Excessive force can damage potentiometerS SO+ Set 10V
controls.C7400 SO Free Use a small screwdriver when adjusting enthalpy + SR+ Cool
StepCheckout Procedure Proper Response
Disconnect power at TR and TR1.All LED are off; Exhaust Fan contacts are open. Disconnect devices at P and P1. Jumper P to P1 (defaults to on board MIN POS potentiometer). Place 5.6K ohm resistor across T and T1 (Blue sleeve- provides input to economizer that the MAT is between 50-55F). Jumper TR to 1 (call for cooling from the thermostat). W7212 only: Jumper TR to N (places economizer in occupied mode). If connected, remove C7
Execute step one, Checkout Preparation.— Turn DCV MAX to mid position. Place 620 ohm resistor across SO and + (white sleeve resistor makes OA — enthalpy low). Place 1.2K ohm resistor across SR and + (purple sleeve resistor makes RA Free cool LED turns on; motor drives to approximately 45 degrees (half)
enthalpy high).open.
Remove 620 ohm resistor from SO and +.Free cool LED turns off; motor drives closed
Turn DCV MAX to mid position.Motor drives to mid position, 45 degrees open.
Turn MIN POS fully CW.Motor drives fully open.
Turn MIN POS and DCV MAX to fully CCW.Motor drives closed.
Adjust DCV MAX towards CW.Motor will move to position set by DCV MAX pot.
Adjust DCV MAX to fully CCW.Motor will drive closed. Reconnect jumper to N terminal.
Adjust DCV MAX and MIN POS pots.Motor will drive to the most open position of the pots. Adjust DCV MAX and MIN POS pots to fully CCW. Remove power from N terminal adjust MIN POS towards CW Motor should not move.
Turn MIN POS to fully CCW.Actuator drives fully closed.
W7212: Remove jumper from TR and N.Actuator drives fully closed. W7214: Jumper TR to O.
W7213: Jumper TR to B.Free cool LED turns off.
W7214: Remove jumper from TR and O.Actuator drives fully closed. ® U.S. Registered Trademark
Toronto, Ontario M1V 4Z9© 2010 Honeywell International Inc. 63-2596—09 M.S. Rev. 03-10
customer.honeywell.comPrinted in U.S.A.

* 規格以原廠最新 Datasheet 為準。

下載完整PDF規格書

外形尺寸

HBT-BMS-W7212-W7213-W7214 外形尺寸圖 詳見圖示|Unit: mm

詳見圖示|Unit: mm

防盜報警安裝工程服務

HKEZIT 專營裝ALARM、裝防盜、裝警鐘工程,HBT-BMS-W7212-W7213-W7214 由我們供貨、安裝、調試到使用教學一站式完成。無論裝ALARM、裝防盜或裝警鐘,均由自家工程團隊上門施工,品質有保證。

裝ALARM裝防盜裝警鐘

防盜報警適合邊類專業客戶

HBT-BMS-W7212-W7213-W7214 honeywell Economizer Logic Modules亦適合以下專業服務機構使用,保安同合規要求同一般商鋪唔一樣,歡迎查詢度身方案。

心臟科診所

心電圖同貴重心臟監測儀器防盜,診症室私隱合規佈點,配合預約系統。

WhatsApp 查詢 →

牙科診所

診症室私隱合規佈點、X光及貴重牙科儀器防盜,配合預約系統減少候診糾紛。

WhatsApp 查詢 →

會計師行

審計旺季外勤同事考勤管理、財務資料室保安,同會計師行嘅合規要求相符。

WhatsApp 查詢 →

知識產權/專利代理

未公開專利同商業機密文件保安要求極高,防止資料外洩爭議。

WhatsApp 查詢 →

企業秘書/稅務顧問公司

大量客戶公司機密檔案室保安,稅季外勤同事出入記錄管理清晰。

WhatsApp 查詢 →

珠寶鑑定/拍賣行

高值品鑑定過程近攝存證,配合保險公司要求,防止調換或盜取。

WhatsApp 查詢 →

常見問題

HBT-BMS-W7212-W7213-W7214 香港哪裡有代理?

HKEZIT 提供原廠行貨連保養,HBT-BMS-W7212-W7213-W7214 原廠行貨連保養,提供上門評估、安裝、防區設定及使用教學一站式服務,全港 32 區均有服務。

此設備適合什麼場景?

詳細規格請參閱上方規格表;我們會按現場環境(商舖、辦公室、倉庫、住宅)設計防區及感應器布局,並提供整體方案報價。

觸發警報後如何通知?

可按需求配置本地警號、手機 App 推送或短訊通知;亦可與 CCTV 聯動,觸發時自動錄影存證。

HBT-BMS-W7212-W7213-W7214 定 MODEL-811FM-TWO-WIRE-GAGE-ABSOLUTE-PRESS 邊個好?

兩者屬同系列產品,實際應該邊個型號更適合,需視乎現場環境同需求而定。歡迎直接聯絡我們免費現場評估,由工程師建議最合適方案。

HBT-BMS-W7212-W7213-W7214 保養、維修邊度做?

HKEZIT 提供 HBT-BMS-W7212-W7213-W7214 原廠行貨連保養,安裝後如有故障可直接聯絡我們安排上門維修,毋須自行聯絡原廠。詳情請參閱防盜報警安裝工程頁面或聯絡我們查詢保養範圍。

香港安裝服務地區

HKEZIT 於全港各區提供 HBT-BMS-W7212-W7213-W7214 honeywell Economizer Logic Modules供貨連專業安裝服務(裝ALARM、裝防盜、裝警鐘),熱門地區包括:大圍防盜報警系統安裝大埔防盜報警系統安裝大角咀防盜報警系統安裝將軍澳防盜報警系統安裝尖沙咀防盜報警系統安裝屯門防盜報警系統安裝旺角防盜報警系統安裝柴灣防盜報警系統安裝。港島、九龍、新界全港 32 區均有上門安裝,歡迎聯絡我們查詢 HBT-BMS-W7212-W7213-W7214 香港價格連安裝報價。

防盜報警適用場景

HBT-BMS-W7212-W7213-W7214 honeywell Economizer Logic Modules適合多種場景使用,以下為部分常見安裝場景,歡迎查詢是否適合您的現場環境。

查看更多防盜報警適用場景,請參閱 防盜報警安裝工程

相關產品

如需整套防盜報警方案,請參閱 防盜報警安裝工程

查詢 HBT-BMS-W7212-W7213-W7214 連安裝價格

免費上門評估,即日報價,原廠行貨保養

立即查詢